Problems - Causes - Remedies signalled by LED indicators
No.
Faults
34
Not used
35
Internal processor timeout
36
Internal processor timeout
37
Combustion air check timeout
38
Internal processor timeout
39
Internal processor timeout
40
Internal hardware fault
41
Internal hardware fault
42
Main processor fault
43
Supervisor processor fault
44
Supervisor processor timeout
45
Off-specification mains voltage
46
Off-specification mains voltage
47
UV: Internal fault
48
Supervisor processor fault
49
Main processor fault
50
Ignition feedback fault
51
Pilot feedback fault
52
Piloted valve feedback fault
53
Actuator feedback waiting time
expired
54
Direct ignition valve feedback
fault
55
Internal processor fault
56
UV: false flame during operation False flame detected before ignition
57
FR: false flame during operation
58
T8 inlet fault
59
Internal hardware fault
60
Local reset fault
61
Open POC fault
62
UV: strong UV flame fault
63
Internal hardware fault
20169372
Cause
Internal fault
Internal fault
The system could not perform verification
tests of the combustion air during the burner
sequence
Internal fault
Internal fault
Internal fault
Internal fault
Internal fault
Internal fault
Internal fault
Off-specification mains voltage/frequency
Off-specification mains voltage/frequency
Internal fault
Internal fault
Internal fault
The system detected the presence of
voltage on T16 at the wrong moment or
there is no voltage when necessary
The system detected the presence of
voltage on T17 at the wrong moment or
there is no voltage when necessary
The system detected the presence of
voltage on T19 at the wrong moment or
there is no voltage when necessary
No actuator feedback on T8 for more than
10 minutes
The system detected the presence of
voltage on T18 at the wrong moment or
there is no voltage when necessary
Internal fault
False flame detected before ignition
The system detected the presence of
voltage on T8 at the wrong moment or there
is no voltage when necessary
Internal fault
Local reset button pressed for more than 10
seconds or reset button locked
The fuel valve is open at the wrong moment Check the wiring
The flame sensor is too close to the flame
Internal fault
40
GB
Solution
Replace the control device
Replace the control device
Check the wiring or the air pressure switch
Replace the control device
Replace the control device
Replace the control device
Replace the control device
Replace the control device
Replace the control device
Replace the control device
Check the mains voltage level or the
frequency. Contact the factory if the
problem persists
Check the mains voltage level or the
frequency.
Contact the factory if the problem persists
Replace the control device
Replace the control device
Replace the control device
Check the wiring and make sure that the
earthing is appropriate
If
the
problem
persists,
distributor/factory
Check the wiring and make sure that the
earthing is appropriate. If the problem
persists, contact the distributor/factory
Check the wiring and make sure that the
earthing is appropriate
If
the
problem
persists,
distributor/factory
Check the wiring
Check the modulation equipment
Check the wiring and make sure that the
earthing is appropriate. If the problem
persists, contact the distributor/factory
Replace the control device
Check the flame sensor
Check the wiring
Check the flame sensor
Make sure that earthing is appropriate
Check the wiring
Check the actuator
Replace the control device
If the problem persists, replace the control
device
Increase the distance between the flame
sensor and the flame OR use an orifice to
reduce the view field
Replace the control device
contact
the
contact
the
Tab. P