Problem
Potential Causes
RO production cycle
not starting as tank
drops
Recirculation fl ow
switch not closing
Re-pressurization
pump fl ow switch
Tank level sensor is disconnected or
has failed
The PLC calibration screen which
allows the system to function is set
for an incorrect storage tank height
storage tanks.
The 0-5 psi sensor allow use of tanks
up to 11.5 foot tall if needed for a non-
standard installation.
This switch will not close if the RO
pump pressure is less than 70 psi.
Repress pump does not turn on
Valve D is not opening
Too much resistant after Valve D
Solution
Verify the connector pin (longer pin connect to GND),
drain tank and replace sensor if necessary
Re-span tank to recalibrate level sensor
Increase production fl ow rate in the HMI setting
screen.
Verify switch operation by removing switch and
manually activating the switch to ensure the switch
closes as fl ow increases
Enter MANUAL mode and bump start transfer pump
Ensure the plumbing line is not shut off by a ball valve
or other impedance further downstream