Thermistor Installation; Duct Connections - Seeley Braemar Invertair SACV10D1S Installation Manual

True inverter add-on cooling unit
Hide thumbs Also See for Braemar Invertair SACV10D1S:
Table of Contents

Advertisement

INDOOR COOLING COIL UNIT DIMENSIONS cont.

THERMISTOR INSTALLATION

Must be installed:
• In the supply air duct in a common air flow- this is an airflow that is not zoned
• Installed centrally at the top of the duct
• The heating thermistor is installed at the inlet of the cooling coil
• The cooling thermistor is installed at the outlet of the cooling coil
COOLING COIL INSTALLATION
• To be installed within 1.5 to 2.5 metres from the heater supply air outlet
• To be installed at the same height as the heater supply air outlet
Cooling Coil
Heater
• The ducting between the heater and coil should be straight and provide no resistance to airflow.

DUCT CONNECTIONS

Attach panels and transitions to heater - as supplied in Kit.
LEGEND
1 - Place louvre infill panel (A) on air outlet end of heater.
2 - Place plain infill panel (B) on air inlet side of heater.
3 - Attach heater transition assemblies (C) to heater. Return must be connected to non-motor side of the fan as shown.
4 - Square sides of transitions and secure with self drilling screws supplied in kit.
Heater
Cooling Coil
Cooling Coil
Heater
ILL1993-A
SEELEY INTERNATIONAL - INSTALLATION MANUAL |
9