Huawei NetCol8000-C190 User Manual page 48

In-room chilled water smart cooling product
Hide thumbs Also See for NetCol8000-C190:
Table of Contents

Advertisement

NetCol8000-C190 In-room Chilled Water Smart
Cooling Product
User Manual (2022, Singapore STT)
● The chilled water pipes should be closely wrapped with thermal insulation
foam along the route. Ensure that the foam is in close contact with the pipes.
● Pipes can be routed from the left or right, depending on the model.
● Ensure that pipes and cables are routed correctly and through different holes.
● After pipes are routed for the unit, seal the gaps between the pipes and the
pipe holes.
To minimize the noise due to vibration of the unit, perform the following
operations:
Figure 3-15 Support layout (unit: mm)
Table 3-8 Port dimensions
Model
NetCol8000-C
Issue 02 (2022-03-30)
NO TICE
When the direction of the chilled water pipes is changed, add a support at the
position that is 1000 mm away from the changing point.
If the chilled water pipes are straight, add a support every 2500 mm.
NO TE
Onsite personnel are responsible for preparing the required materials and installing the
supports.
NO TE
● Left pipe routing is used as an example.
● Install the chilled water inlet pipe and then the chilled water outlet pipe.
Copyright © Huawei Technologies Co., Ltd.
Port Dimensions of a
Chilled Water Inlet Pipe
G 2 inch, thread
connection
3 Installation
Port Dimensions of a
Chilled Water Outlet
Pipe
G 2 inch, thread
connection
40

Advertisement

Table of Contents
loading

This manual is also suitable for:

Netcol8000-c190d40edNetcol8000-c190d40ec

Table of Contents