Setting Parameters (WB1F)

The setting parameters and setting values necessary for the PLC connection are as follows:
Adjust the setting according to the using environment.
All the settings of the WB1F should be performed before using the PLC connection.
z
When the device of setting the WB1F (as PC) is different from the device to be connected through the PLC
z
connection, prepare a cable supporting both devices.
Do not access or change any settings that are not listed here.
z
Do not access or change any settings in reserved areas.
z
When the setting values have been changed, save the setting value by "Save Set Values" on the control com-
z
mand.
Turning OFF the power, resetting, or changing the operation mode without performing "Save Set Values"will
return to the setting value that existed before change.
When configuring settings that specify ASCII code for the setting value, be aware of the following points.
NUL (00H) cannot be used as a setting value.
z
The characters up to the first NUL (00H) are considered the data and any data after that is not valid.
z
Setting value (hex) of bold face is default value (Setting at the time of factory shipments).
Item
Sub item
Communication
speed
RS-232 setting
Data length
Parity
Stop bits
Flow control
Function enabled
PLC
Connection
Protocol Select
Monitoring cycle
Timeout
2 Operation Specifications
Address
Size
(hex)
(dec)
0100
1
0101
1
0102
1
0103
1
0104
1
06C0
1
06C1
1
06C2
1
06C3
1
1-3
3 Setting and Wiring
Default
Setting value
(hex)
(hex)
00 :
1,200bps
01 :
2,400bps
02 :
4,800bps
03 :
9,600bps
03
04 :
19,200bps
05 :
38,400bps
06 :
57,600bps
07 : 115,200bps
0a :
600bps
00 : 7bits
01
01 : 8bits
00 : NONE
01 : EVEN
01
02 : ODD
00 : 1bit
00
01 : 2bits
00 : NONE
00
01 : CTS/RTS
00 : Disabled
00
01 : Enabled
00 : MC Protocol Format
00
4 4C (Q,L Series)
01 - FF : Setting Value × 10ms
0A
(10ms to 2,550ms)
01 - FF : Setting Value × 100ms
14
(100ms to 25,500ms)
4 Menu Sheet
Setting Parameters (WB1F)
Remarks
After saving, the settings are
reflected when the power is
turned on, the WB1F is reset,
or the operation mode is
changed.
If enabled, it will begin
the process to establish a
connection with connected
external devices at start up.
New settings will be reflected
after saving and resetting the
device.
Select the communication
protocol of the external device
that is to be connected to the
WB1F.
Configure the monitoring
interval for the special area.
Configures response timeout
from a PLC.