Riello FS5 LME Installation, Use And Maintenance Instructions page 15

Forced draught gas burner
Table of Contents

Advertisement

Signal
10 blinks
The burner does not
switch on, and the
lockout appears
The burner goes into
lockout
No blink
The burner does not
start
The burner continues
to repeat the start-up
cycle, without lockout
Ignition with pulsations 43 - Poorly adjusted head . . . . . . . . . . . . . . . .
N.B.: If problems still occur after all of the above checks have been made, check the electrical connec-
tions on the plug and sockets, the damper and burner motor, gas control wiring ignition transformer
and external interlocks, if the burner still fails to function, replace the control box.
20039410
Problem
32 - Incorrect electrical wiring . . . . . . . . . . . . .
33 - Defective control box . . . . . . . . . . . . . . . .
34 - Presence of electromagnetic . . . . . . . . .
disturbances in the thermostat lines
35 - No electrical power supply. . . . . . . . . . . .
36 - A limiter or safety control device is open .
37 - Line fuse blocked. . . . . . . . . . . . . . . . . . .
38 - Defective control box . . . . . . . . . . . . . . . .
39 - No gas supply . . . . . . . . . . . . . . . . . . . . .
40 - Mains gas pressure insufficient . . . . . . . .
41 - Minimum gas pressure switch fails to . . .
close
42 - The gas pressure in the gas mains lies
very close to the value to which the mini-
mum gas pressure switch has been set.
The sudden drop in pressure after valve
opening causes temporary opening of the
pressure switch itself, the valve immedi-
ately closes and the burner comes to a
halt. Pressure increases again, the pres-
sure switch closes again and the ignition
cycle is repeated. And so on
44 - Ignition electrode incorrectly adjusted . . .
45 - Incorrectly adjusted fan air damper: too
much air
46 - Output during ignition phase is too high .
Possible cause
13 GB
Recommended remedy
Check
Replace
Filter or eliminate
Close all switches - Check connec-
tions
Adjust or replace
Replace
Replace
Open the manual valves between
contactor and train
Contact your GAS COMPANY
Adjust or replace
Reduce the minimum gas pressure
switch intervention pressure.
Replace the gas filter cartridge.
Adjust. See page 6
Adjust, see page 4
Adjust
Reduce

Advertisement

Table of Contents
loading

This manual is also suitable for:

564t31

Table of Contents