Download Print this page

Output Module Application - AB Quality Allen-Bradley 2755-SN3 User Manual

Adaptascan bar code readers

Advertisement

3–20
Installing the Wiring Base and Power Supply

Output Module Application

Shown below is a typical output module application. When
connecting high impedance loads, you may need to add a resistor in
parallel with the load. This resistor (typically 300 to 6,000 ohms)
provides a continuous minimum current flow (10 mA DC or 50 mA
AC) through the output module in the closed state. See Appendix C
for available Allen-Bradley fuse, diode and resistor terminal blocks.
Back Electromotive Force (EMF) is sometimes generated when an
inductive load is switched off. Back EMF may damage the output
module. A diode in parallel with the inductive device dissipates the
back EMF.
Fuse
Recommended
Fuse
Recommended
Load
Optional Resistor
+
AC or DC Source
Inductive
Load
Optional Diode
+
DC Source