I N S T A L L A T I O N
Ventilation
• Make sure that the compressor always has a sufficient amount of fresh air available for cooling.
• To prevent serious damage, ensure that the cooling air flow can flow freely.
• The necessary cooling air flow can be calculated by using the following formula:
300 x drive power [kW] = required cooling air flow [m³/h]
Example 11kW motor: 300 x 11kW = 3300 m³/h = required cooling air flow.
• The fan capacity for fresh air and warm air must meet at least the required cooling air flow.
The fans must have the same capacity.
Fig. Ventilation through facade
Fig. Ventilation via ventilation stack
LW SC-300 E / LW SC-350 E
Version: 06.12.2022
A
Page A - 21