Power Protections - ABB SACE Emax 2 Instructions Manual

Emax low voltage air circuit-breakers e1.2-e2.2-e4.2-e6.2
Table of Contents

Advertisement

6 - Power protections

List
The Power protections, available by default for Ekip Hi-Touch, Ekip G Touch, Ekip G-Hi Touch models and configurable in Ekip Touch as additional
SW package, are:
Name
Type of protection
RP
Reverse active power
D
(2)
Directional short-circuit with adjustable delay
OQ
Maximum reactive power
(1)
OP
Active overpower
(1)
UP
Active underpower
(1)
RQ
(1)(2)
Reverse reactive power
CosΦ
Minimum cosφ
Further details about the protections are given in document 1SDH001330R1002.
(1)
the protection is not available by default with Ekip Hi-Touch. However, it can be integrated by requesting the relative SW package
the protection is not available by default with Ekip G Touch. However, it can be integrated by requesting the relative SW package
(2)
Block configuration available via Ekip Connect
(3)
(4)
Directional Zone Selectivity functions as an alternative to Zone Selectivity S and G
WARNING! The Power flow parameters effect the sign of the power and power factor values measured by the unit. Power flow
must be configured and verified on the basis of your installation to ensure that all the protections of the Power Protections
package function correctly
Summary table
ABB
ANSI
Threshold
(7)
P11 = -1...-0,05 Sn step =
RP
32R
0,001 Sn
I7 Fw/Bw = 0,6...10 In step
D
67
(8)
= 0,1 In
Q27 = 0,4...2 Sn step =
OQ
32OF
0,001 Sn
P26 = 0,4...2 Sn step =
OP
32OF
0,001 Sn
P23 = 0,1...1 Sn step =
UP
32LF
(9)
0,001 Sn
Q24 = -1...-0,1 Sn step =
0,001 Sn; Kq = -2...2 step
RQ
40 / 32R
= 0,01; Vmin = 0,5...1,2 Un
step = 0,01
Cosφ = 0,5...0,95 step =
CosΦ
78
0,01
calculation of t
is valid for values which have exceeded the trip threshold of the protection
(5)
t
(6)
tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current values
within operating limits; the tolerance value is ± 20% if the conditions are not guaranteed
ANSI / IEEE C37-2 codification
(7)
(8)
the protection does not detect the fault current direction for < 5 V voltages.
not active if the circuit-breaker is open (TRIP OFF is signaled); the protection is also active for negative active power, but is independent
(9)
of RP protection (Protection from inverse active power)
22 | © 2023 ABB | 1SDH001316R1002 - ECN000297030
Threshold
Tolerance
Time
threshold
t11 = 0,5...120 s
± 10 %
step = 0,01 s
t7 Fw/Bw =
± 7 % If ≤ 6 In
0,1...0,8 s step =
± 10 % If > 6 In
0,01 s
t27 = 0,5...100 s
± 10 %
step = 0,5 s
t26 = 0,5...100 s
± 10 %
step = 0,5 s
t23 = 0,5...100 s
± 10 %
step = 0,5 s
t24 = 0,5...100 s
± 10 %
step = 0,5 s
-
-
Time
Additional functions
Trip enable, Block
Trip enable, Directional Zone Selectivity
Startup enable, Block, Direction Min Angle
Trip enable, Block
Trip enable, Block
Trip enable, Block, Startup enable
Trip enable, Block
Calculation
formula t
Tolerance t
(5)
t
The best of the two values: ± 10% or ±
t
= t11
40 ms (for set time < 5 s) / ± 100 ms (for
t
set time ≥ 5 s)
± 40 ms (for t7 ≥ 400 ms) / whichever is
t
= t7
higher, ± 20 ms or ± 10 % (for t7 < 400
t
ms)
The best of the two values: ± 10% or ±
t
= t27
40 ms (for set time < 5 s) / ± 100 ms (for
t
set time ≥ 5 s)
The best of the two values: ± 10% or ±
t
= t26
40 ms (for set time < 5 s) / ± 100 ms (for
t
set time ≥ 5 s)
The best of the two values: ± 10% or ±
t
= t23
40 ms (for set time < 5 s) / ± 100 ms (for
t
set time ≥ 5 s)
The best of the two values: ± 10% or ±
t
= t24
40 ms (for set time < 5 s) / ± 100 ms (for
t
set time ≥ 5 s)
-
-
ABB | SACE Emax 2
ABB | SACE Emax 2
(3)
,
(4)
(6)
t
Continued on the next page