3 - Voltage protections

List
The Voltage protections, available by default for Ekip Hi-Touch, Ekip G Touch, Ekip G-Hi Touch models and configurable in the remaining models
as additional SW package, are:
Name
Type of protection
UV
Minimum voltage
OV
Maximum voltage
UV2
Minimum voltage
(1)
OV2
Maximum voltage
(1)
VU
Voltage unbalance
Phase Sequence
Phase sequence error
Further details about the protections are given in document 1SDH001330R1002.
protections UV2 and OV2 are not available by default with Ekip G Touch. However, they can be integrated by requesting the relative SW
(1)
package
Block configuration available via Ekip Connect
(2)
Summary table
ABB
ANSI
Threshold
(5)
U8 = 0,5...1 Un
UV
27
Step = 0,001 Un
U9 = 1...1,5 Un Step
OV
59
= 0,001 Un
U15 = 0,5...1 Un
UV2
27
Step = 0,001 Un
U16 = 1...1,5 Un
OV2
59
Step = 0,001 Un
U14 = 2...90 % Step
VU
47
(6)
= 1 %
Phase
47
1-2-3 / 3-2-1
Sequence
(3)
calculation of t
is valid for values which have exceeded the trip threshold of the protection
t
tolerance values valid with Trip unit supplied at full rate or by auxiliary power supply, trip time ≥ 100 ms, temperature and current values
(4)
within operating limits; the tolerance value is ± 20% if the conditions are not guaranteed
(5)
ANSI / IEEE C37-2 codification
protection not active if the higher of the voltages measured is less than 0.3 Un
(6)
the trip unit considers 3% hysteresis for quitting alarm condition
(7)
19 | © 2023 ABB | 1SDH001316R1002 - ECN000297030
Th-
reshold
Tolerance
Time
threshold
t8 = 0,05...120 s
± 2 %
(7)
Step = 0,01 s
t9 = 0,05...120 s
± 2 %
(7)
Step = 0,01 s
t15 = 0,05...120 s
± 2 %
(7)
Step = 0,01 s
t16 = 0,05...120 s
± 2 %
(7)
Step = 0,01 s
t14 = 0,5...60 s
± 5 %
Step = 0,5 s
Time
Additional functions
Trip enable, Block
Trip enable, Block
Trip enable, Block
Trip enable, Block
Trip enable, Block
Calculation
Tolerance t
formula t
(3)
t
The best of the two values: ± 10% or ±
t
= t8
40 ms (for set time < 5 s) / ± 100 ms (for
t
set time ≥ 5 s)
The best of the two values: ± 10% or ±
t
= t9
40 ms (for set time < 5 s) / ± 100 ms (for
t
set time ≥ 5 s)
The best of the two values: ± 10% or ±
t
= t15
40 ms (for set time < 5 s) / ± 100 ms (for
t
set time ≥ 5 s)
The best of the two values: ± 10% or ±
t
= t16
40 ms (for set time < 5 s) / ± 100 ms (for
t
set time ≥ 5 s)
The best of the two values: ± 10% or ±
t
= t14
40 ms (for set time < 5 s) / ± 100 ms (for
t
set time ≥ 5 s)