INSTRUCTION MANUAL
GNExS1
Alarm Horn Sounder with relay / telephone initiate
For use in Flammable Gas Atmospheres
2) Warnings
 DO NOT OPEN WHEN ENERGISED.
 DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS
PRESENT.
 POTENTIAL ELECTROSTATIC CHARGING HAZARD.
 ALL ENTRIES M20 X 1.5MM.
 IF TEMPERATURE EXCEEDS 70°C AT ENTRY OR 80°C
AT BRANCHING POINT USE SUITABLE RATED CABLE
AND CABLE GLANDS.
 IF OPENING THE UNIT DURING MAINTENANCE
OPERATIONS A CLEAN ENVIRONMENT MUST BE
MAINTAINED AND ANY DUST LAYER REMOVED PRIOR
TO OPENING THE UNIT.
3) Marking & Rating Information
All units have a rating label, which carries the following
important information.
Products may have further approvals, see E2S website for
further details.
ATEX / IECEx / UKEX Ratings
Standards
EN60079-0:2018 EN IEC60079-0:2018
General Requirements
EN60079-1:2014 A/C:2018 EN 60079-1:2014 ed. 7
Flameproof Enclosure 'd'
Model No:
GNExS1DC024-T
Ex db IIC T4 Gb for Ta –60°C to +50°C
GNExS1AC230-T
Ex db IIC T3 Gb for Ta –60°C to +70°C
Ex db IIB T6 Gb for Ta –60°C to +50°C
Ex db IIB T5 Gb for Ta –60°C to +65°C
Ex db IIB T4 Gb for Ta –60°C to +70°C
Certificate No.
SIRA 13ATEX1139X
IECEx SIR 13.0029X
CSAE 21UKEX1558X
Epsilon x
Equipment Group
and Category:
CE Marking and
Notified Body No.
UKCA Marking and
Notified Body No.
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. D157-00-681-IS
Rating
II 2G
2813
0518
Issue 1
27-04-2023
4) Zones, Gas Group, Category and
Temperature Classification
The units can be installed in locations with the following
conditions:
Area Classification
Explosive gas air mixture likely to occur in
Zone 1
normal operation.
Explosive gas air mixture not likely to occur in
Zone 2
normal operation, and if it does, it will only exist
for a short time.
Gas Groupings
Group IIA
Propane
Group IIB
Ethylene
Group IIC
Hydrogen and Acetylene
Temperature Classification for Gas Applications
T1
450
o
C
o
T2
300
C
T3
200
o
C
T4
135
o
C
T5
100ºC
T6
85ºC
Equipment Category
2G
Ambient Temperature Range
GNExS1
-60°C to +70°C
IP6X to EN/IEC60079-0
IP66 to EN60529
www.e2s.com