Wired Controller CDV-46
Parameter
Parameter name
code
Set quantity of
P14
group control
indoor units
Set unit of
P16
temperature
Set static pressure
P30
of indoor fan motor
High ceiling
P31
installation*
P33
Set Timer
Parameter
range
00: forbid this
function
01-16: indoor unit
quantity
00:Celsius
01:Fahrenheit
01-09: static pressure
level of indoor fan
motor
00: installation height
of standard ceiling
01: installation height
of high ceiling
00: general timer
01: clock timer
28
Default
Note
value
Set the corresponding value
01
according to the connected
indoor unit quantity.
00
There are two kinds of static
pressure level:
5 levels: 03, 04, 05, 06, 07
9 levels: 01, 02, 03, 04, 05,
06, 07, 08, 09
Wired controller can be
adapted to the different types
of indoor units that it
possesses 1-9 level selection
05
for setting static pressure.
When the indoor unit with 5
static pressure levels
received the level setting
sent by wired controller is
less than 3, it will be settled
as the 3rd level; if it is over 7,
it will be settled as the 7th
level.
Only applicable to cassette
00
units
00
--
--