Outdoor Temperature Sensor Error - Fujitsu AB A30LBT Series Service Instruction

Hide thumbs Also See for AB A30LBT Series:
Table of Contents

Advertisement

Trouble shooting 7
OUTDOOR UNIT Error Method:

Outdoor Temperature Sensor Error

Detective Actuators:
Outdoor Unit Main PCB Circuit
Outdoor Temperature Thermistor
Forecast of Cause:
1. Connector connection failure 2.Thermistor failure 3. Main PCB failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>> Upon correcting the removed connector or mis-wiring, reset the power.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Approx. value)
Temperature
(°C )
Resistance Value (k )
Temperature
(°C )
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
BROWN
1
1
CN 64
2
2
BROWN
3
3
BLUE
1
1
CN 62
2
2
BLUE
3
3
BROWN
1
1
CN 63
2
2
BROWN
3
3
BLACK
1
1
CN 65
2
2
BLACK
3
3
If the voltage does not appear, replace Main PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When Outdoor Temperature Thermistor open or short-circuit is
detected at power ON or while running the compressor.
-20
-10
-5
115
62.3
46.6
30
40
50
7.97
5.18
3.45
THERMISTOR
( COMPRESSOR TEMP. )
THERMISTOR
( OUTDOOR TEMP. )
THERMISTOR
( DISCHARGE PIPE )
THERMISTOR
( HEAT EXCHANGER )
02-11
0
5
10
35.2
26.9
20.7
60
70
2.36
1.65
15
20
16.1
12.6
DC