Hmi Panel Drawings; Connectors; Communication Ports - Beijer Electronics X2 control 10-B2 Hardware And Installation Manual

Table of Contents

Advertisement

HMI Panel Drawings

6. HMI Panel Drawings

6.1. Connectors

1
2
Pos
Connector
1
Power supply
2
Digital out
3
USB
4
LAN A
5
LAN B
6
COM

6.1.1. Communication Ports

Pin
COM 1
1
2
RS-232 RxD
3
RS-232 TxD
4
5
GND
6
7
RS-232 RTS
8
RS-232 CTS
9
The connector supports up to three independent communication channels and can be configured for
RS-232 and RS-422 or 2x RS-485 or 2x CAN.
NOTE
In order to utilize two communication ports, the Y-split cable CAB109 can be used.
To use RS-232 and RS-422, use CAB 109.
2024-01
3
4
5
6
+24 V DC (18–32 V DC)
Opto-MOS relay, 2x SPST. Normally open, isolated.
USB Host 2.0, max output current 500 mA
1×10/100 Base-T (shielded RJ45)
1×10/100 Base-T (shielded RJ45)
Serial communication port
D-sub-9, female
COM 2
RS-422 Tx+
RS-485 Tx+/Rx+
RS-422 Rx+
GND
RS-422 Tx-
RS-485 Tx-/Rx-
RS-422 RX-
18
Description
COM 3
CAN 1
CAN 1-H
RS-485 Tx+/Rx+
GND
GND
CAN 1-L
RS-485 Tx-/Rx-
Beijer Electronics, MAEN221
CAN 2
CAN 2-H
GND
CAN 2-L