Mitsubishi Electric Mr. SLIM PCA-M KA Series Installation Manual page 11

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 3
6. Electrical work
Service menu
Test run
Input maintenance info.
Settings
Check
Others
Main menu:
Cursor
F1
F2
F3
F4
Fig. 6-2
Function setting
Ref. address
Unit No.
Grp./1/2/3/4/All
Monitor:
Cursor
Address
F1
F2
F3
F4
Fig. 6-4
Function setting
Ref. address
Grp.
1/8
Mode 1
Mode 2
Mode 3
Mode 4
Request:
Value
F1
F2
F3
F4
Fig. 6-6
Settings menu
Function setting
Rotation setting
Service menu:
Cursor
F1
F2
F3
F4
Fig. 6-3
Function setting
Ref. address
Grp.
1/8
Mode 1
Mode 2
Mode 3
Mode 4
Save:
Cursor
Page
F1
F2
F3
F4
Fig. 6-5
Function setting
Ref. address
Grp.
Sending data
F1
F2
F3
F4
Fig. 6-7
6.2. Function setting
6.2.1. Function setting on the unit (Selecting the unit functions)
1 (Fig. 6-2)
• Select "Service" from the Main menu, and press the [SELECT] button.
• Select "Settings" from the Service menu, and press the [SELECT] button.
2 (Fig. 6-3)
• Select "Function setting" with the [SELECT] button.
3 (Fig. 6-4)
• Set the indoor unit refrigerant addresses and unit numbers with the [F1]
through [F4] buttons, and then press the [SELECT] button to confirm the cur-
rent setting.
<Checking the Indoor unit No.>
When the [SELECT] button is pressed, the target indoor unit will start fan
operation. If the unit is common or when running all units, all indoor units for the
selected refrigerant address will start fan operation.
4 (Fig. 6-5)
• When data collection from the indoor units is completed, the current settings
appears. Screen appearance varies depending on the "Unit No." setting.
• Toggle through the pages with the [F3] or [F4] button.
• Select the mode number with the [F1] or [F2] button, and then press the [SE-
LECT] button.
5 (Fig. 6-6)
• Select the setting number with the [F1] or [F2] button.
Setting range for modes 1 through 28: 1 through 3
Setting range for modes 31 through 66: 1 through 15
6 (Fig. 6-7)
• When the settings are completed, press the [SELECT] button to send the set-
ting data from the remote controller to the indoor units.
• When the transmission is successfully completed, the screen will return to the
Function setting screen.
Note:
• Make the above settings on Mr. Slim units as necessary.
• Function table summarizes the setting options for each mode number.
• Be sure to write down the settings for all functions if any of the initial set-
tings has been changed after the completion of installation work.
en
9

Advertisement

Table of Contents
loading

Table of Contents