Mitsubishi Electric PUZ-SM100VKA2 Service Manual page 62

Table of Contents

Advertisement

Type of
Switch
No.
Switch
1
SW5
2
3,4,5,6
1
2
3
SW7
*4
4
5
6
1
SW8
2
3
1
SW9
2
3,4
1
Dip
2
switch
3
4
5
SW6
6
7
8
*
2
'Power failure automatic recovery' can be set by either remote controller or this DIP SW. If one of them is set to ON, 'Auto
recovery' activates. Please set "Auto recovery" basically by remote controller because not all units have DIP SW.
Please refer to the indoor unit installation manual.
*
3
SW7-1,2 are used for demand control. SW7-1,2 are effective only at the demand control.
(Refer to the next page : Special function (b))
*
4
Please do not use SW7-3 to 7-5 usually. Trouble might be caused by the usage condition.
*
5
SW6-1 to 3: Function switch.
OCH774A
Function
No function
Power failure
automatic recovery
*2
No function
Model select
*3
No function
Max Hz setting (cooling)
Max Hz (cooling) × 0.8
Max Hz setting (heating) Max Hz (heating) × 0.8
No function
Defrost Hz setting
No function
No function
No function
No function
Function switch
No function
No function
No function
Fan motor check mode
Model select
Action by the switch operation
ON
Auto recovery
No auto recovery
Demand function
Low noise mode
For high humidity
Valid
ON
*5
MODEL
SW6-4, 5, 6, 7, 8
ON
100V
OFF
1 2 3 4 5 6 7 8
ON
125V
OFF
1 2 3 4 5 6 7 8
ON
140V
OFF
1 2 3 4 5 6 7 8
ON
100Y
OFF
1 2 3 4 5 6 7 8
ON
125Y
OFF
1 2 3 4 5 6 7 8
ON
140Y
OFF
1 2 3 4 5 6 7 8
62
Effective timing
OFF
When power supply ON
Always
Normal
Always
Normal
Always
Normal
Always
Normal
Always
When power supply ON
OFF
during test run