Xcc System Management Port Leds - Lenovo ThinkSystem SR950 V3 System Configuration Manual

Hide thumbs Also See for ThinkSystem SR950 V3:
Table of Contents

Advertisement

Table 20. LEDs description
Scenario
RoT security module fatal
firmware failure
No system power (FPGA
heartbeat LED off)
XCC firmware recoverable
error
XCC firmware is recovered
from error
UEFI firmware authentication
failure
UEFI firmware is recovered
from authentication failure
System is OK (FPGA
heartbeat LED is On)
Note: For locations of the FPGA LED and XCC heartbeat LED, see
page 35
and
"System I/O board LEDs" on page

XCC system management port LEDs

This topic provides information on LEDs of XCC system management port.
The following table describes the problems that are indicated by LEDs on XCC system management port.
Fatal
AP0
AP1
Error
LED
LED
LED
Off
Off
On
Blink
N/A
On
Blink
N/A
On
Off
Off
Off
Blink
N/A
Off
On
N/A
Off
N/A
Blink
Off
N/A
On
Off
On
On
Off
33.
FPGA
XCC
heart-
heart-
beat
beat
note
note
LED
LED
Actions
Replace the Firmware and
N/A
N/A
RoT Security Module.
N/A
N/A
Replace the Firmware and
RoT Security Module.
Replace the Firmware and
On
N/A
RoT Security Module.
Off
Off
If the AC power is on, but the
system board assembly does
not have power, then:
1. Check the power supply
2. If the PSU, PIB, or PDB is
N/A
N/A
Information only. No action is
required.
N/A
N/A
Information only. No action is
required.
N/A
N/A
Information only. No action is
required.
N/A
N/A
Information only. No action is
required.
On
On
Information only. No action is
required.
"Lower processor board (MB) LEDs" on
Chapter 2
unit (PSU), power
interposer board (PIB), or
power distribution board
(PDB). If the PSU, PIB, or
PDB has any error,
replace it.
good, do the following:
a. Replace the system I/
O board.
b. Replace the lower
processor board (MB).
c. Replace the upper
processor board (CPU
BD).
.
Server components
37