Mitsubishi Electric PUZ-SWM60VAA Service Manual page 66

Air to water heat pump units
Table of Contents

Advertisement

SW2 setting
The operation mode when the fourth-to-
last error occurred
ON
1
2 3 4 5 6
The operating frequency when the
ON
fourth-to-last error occurred
0 to 255
1
2 3 4 5 6
The compressor current when the
ON
fourth-to-last error occurred
0 to 50
1
2 3 4 5 6
The primary current when the fourth-to-
last error occurred
ON
0 to 500
1
2 3 4 5 6
The DC bus voltage when the fourth-to-
last error occurred
ON
100 to 1023
1
2 3 4 5 6
The fan step when the fourth-to-last
error occurred
ON
0 to 16
1
2 3 4 5 6
The return water temperature (THW2)
when the fourth-to-last error occurred
ON
0 to 60
1
2 3 4 5 6
The indoor liquid pipe temperature
(TH2) when the fourth-to-last error
ON
occurred
−39 to 88
1
2 3 4 5 6
The indoor pipe temperature/Cond./Eva.
(TH5) when the fourth-to-last error
ON
occurred
−39 to 88
1
2 3 4 5 6
The discharge temperature (TH4) when
the fourth-to-last error occurred
ON
−20 to 217
1
2 3 4 5 6
The outdoor liquid pipe temperature
(TH3) when the fourth-to-last error
ON
occurred
1
2 3 4 5 6
OCH809A
Display detail
The black square (
Explanation for display
This setting shows the operation mode when the
fourth-to-last error occurred as well as the default
setting (Please refer to the following).
(SW2)
ON
1
2 3 4 5 6
0 to 255
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0 to 50
0 to 500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
100 to 1023
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0 to 16
0 to 60
−39 to 88
Indoor liquid pipe temperature (TH2)
Σ(TH2(N))/n
(When it is 0 or less, "–" and numbers are displayed
by turns.)
−39 to 88
Indoor pipe temperature/Cond./Eva. (TH5)
Σ(TH5(N))/n
(When it is 0 or less, "–" and numbers are displayed
by turns.)
−20 to 217
(When it is 0 or less, "–" and numbers are displayed
by turns.)
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
−39 to 88
(When it is 0 or less, "–" and numbers are displayed
by turns.)
66
) indicates a switch position.
Unit
Mode
Hz
A
0.1 A
V
Step
°C
°C
°C
°C
°C