Mitsubishi Electric PUZ-SWM60VAA Service Manual page 65

Air to water heat pump units
Table of Contents

Advertisement

SW2 setting
The indoor liquid pipe temperature
(TH2) when the third-to-last error
ON
occurred
−39 to 88
1
2 3 4 5 6
The indoor pipe temperature/Cond./Eva.
(TH5) when the third-to-last error
ON
occurred
−39 to 88
1
2 3 4 5 6
The discharge temperature (TH4) when
ON
the third-to-last error occurred
−20 to 217
1
2 3 4 5 6
The outdoor liquid pipe temperature
ON
(TH3) when the third-to-last error
occurred
−39 to 88
1
2 3 4 5 6
The outdoor 2-phase pipe temperature
ON
(TH6) when the third-to-last error
occurred
−39 to 88
1
2 3 4 5 6
The ambient temperature (TH7) when
ON
the third-to-last error occurred
−39 to 88
1
2 3 4 5 6
The heat sink temperature (TH8) when
ON
the third-to-last error occurred
−40 to 200
1
2 3 4 5 6
The suction pipe temperature (TH32)
ON
when the third-to-last error occurred
−39 to 88
1
2 3 4 5 6
The Comp. surface temperature (TH33)
when the third-to-last error occurred
ON
−20 to 217
1
2 3 4 5 6
The LEV-A opening pulse when the
ON
third-to-last error occurred
0 to 500
1
2 3 4 5 6
The LEV-B opening pulse when the
ON
third-to-last error occurred
0 to 500
1
2 3 4 5 6
The LEV-C opening pulse when the
ON
third-to-last error occurred
0 to 500
1
2 3 4 5 6
OCH809A
Display detail
65
The black square (
Explanation for display
−39 to 88
Indoor liquid pipe temperature (TH2)
Σ(TH2(N))/n
(When it is 0 or less, "–" and numbers are displayed
by turns.)
−39 to 88
Indoor pipe temperature/Cond./Eva. (TH5)
Σ(TH5(N))/n
(When it is 0 or less, "–" and numbers are displayed
by turns.)
−20 to 217
(When it is 0 or less, "–" and numbers are displayed
by turns.)
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
−39 to 88
(When it is 0 or less, "–" and numbers are displayed
by turns.)
−39 to 88
(When it is 0 or less, "–" and numbers are displayed
by turns.)
−39 to 88
(When it is 0 or less, "–" and numbers are displayed
by turns.)
−40 to 200
(When it is 0 or less, "–" and numbers are displayed
by turns.)
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
−39 to 88
(When it is 0 or less, "–" and numbers are displayed
by turns.)
−20 to 217
(When it is 0 or less, "–" and numbers are displayed
by turns.)
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0 to 500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0 to 500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0 to 500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
) indicates a switch position.
Unit
°C
°C
°C
°C
°C
°C
°C
°C
°C
Pulse
Pulse
Pulse