Page 1
Fire Alarm System Salwico CS3000 Installation manual çConsilium...
Page 2
The contents of this document are subject to revision without notice due to continued progress in methodology, design and manufacturing. Consilium assumes no legal responsibility for any error or damage resulting from the usage of this document. Edition 6, 08 2 E, December 2008.
Installation Manual Contents Salwico CS3000 Contents About this manual ................. ii Chapter 1: Installation Mechanical installation .............. 1-1 Central unit ..................1-1 Section units ..................1-1 Electrical installation ..............1-2 Test the cable ..................1-4 Set the address on the analogue detectors......... 1-6 Set the ID .....................
Page 4
Part B: Loop status ................... 4-2 Part C: Central status ................4-3 Summary....................4-3 Appendix A: Address List/Test Report for Consilium Marine CS3000 Fire Alarm Loop Units Appendix B: Connections for Salwico Analogue Detectors Appendix C: Fault codes Appendix D:...
Installation Manual About this manual Salwico CS3000 About this manual This manual is intended to be used mainly by personnel installing CS3000 fire alarm system. The installation procedure is divided into two parts, the physical installation of the system and the verification of the functions of the system.
Installation Manual Chapter 1: Mechanical installation 1 - 1 Salwico CS3000 Chapter 1: Installation The different parts of the CS3000 fire alarm system, the central unit, the control units, repeaters and the section units, should first be mechanically installed. The different section units are thereafter electrically installed and set up according to the definition of the loops.
Installation Manual Chapter 1: Mechanical installation 1 - 2 Salwico CS3000 Electrical installation A loop may consist of different types and different numbers of section units, the connection to the loop depends on the type of section unit and the configuration of your system. Some of the section units are connected directly to the loop and some via an address unit.
Page 8
Installation Manual Chapter 1: Mechanical installation 1 - 3 Salwico CS3000 RDJ-2(T) TDT-2(K) AE-2(K) AE-2K/I AE-2(K) 57 ° C 80 ° C SWM-1KL UVFD-2 SW-1EX IN FIRE CENTRAL 100 ° C 150 ° C LOOP X PRIMARY SLZ-2 SLZ-2 SECONDARY...
Installation Manual Chapter 1: Mechanical installation 1 - 4 Salwico CS3000 Test the cable The cable should be tested for proper function after all the section units are connected and before the cable is connected to the central unit. The cable can only be tested if all short circuit isolators are bypassed.
Page 10
Installation Manual Chapter 1: Mechanical installation 1 - 5 Salwico CS3000 Test 3: Test for earth failure. Measure between the + pole and the - pole respectively and earth to detect an earth fault. Connect the ohm meter between + pole and earth. Measure and thereafter repeat the procedure for - pole.
Installation Manual Chapter 1: Mechanical installation 1 - 6 Salwico CS3000 Set the address on the analogue detectors An address must be specified for each section unit to make it operational. The address interval for each loop is 1-150. The address is...
Installation manual Chapter 1: Setting the ID 1 - 8 CS3000 Set the ID The ID must be set for the address units, AE-2, AE-2K and AE-2K/I, since the function of the unit depends on this setting. Each device connected to the system has an internal ID which is read and handle by the control unit.
Installation manual Chapter 1: Setting the ID 1 - 9 CS3000 ID switch settings for the address unit See appendix B for an ID list. Set address interval on timer Three different addresses should be set on a timer. All addresses are set on DIP-switches.
Installation manual Chapter 1: Cable requirements 1 - 10 Salwico CS3000 Cable requirements The cable must fulfil the following requirements. We refer to current regulation for the rest of the specification. Loop: Min. 2 x 0.3 mm Sub-loop: Min. 2 x 0.3 mm * The minimum area is only from a technical point of view.
Page 16
Installation manual Chapter 1: Cable requirements 1 - 11 Salwico CS3000 Type 3: Reduced capacity level 2 • All address units with a constant voltage output on the sub-loop (except AE-2E with separate power supply). • AE-2 and AE-2K, configured as smoke detector (ID 111 and 124), flame detector, IR, (ID 123) and heat detector with constant output on the sub-loop (ID 118).
Installation Manual Chapter 1: Connection to central unit 1 - 12 Salwico CS3000 Connection to central unit Terminal layout Since all systems are customer designed there exists no standard for how the different boards are to be connected in the system. However in the figure below you will find one board of each type that can be connected to the CS3000 system.
Page 18
Installation Manual Chapter 1: Connection to central unit 1 - 13 Salwico CS3000 Figure 1-1. An example of a central unit terminal layout...
Installation Manual Chapter 1: Connection to central unit 1 - 14 Salwico CS3000 Terminal description The specification may be subject to changes without notice. Terminal P1 ARK-2 Description Function Voltage Current Terminal Fused supervised output for U: 24 VDC : 2 A...
Page 20
Installation Manual Chapter 1: Connection to central unit 1 - 15 Salwico CS3000 Description Function Voltage Current Terminal GA relay : 50 VAC, 32 VDC : 2 A P1:22 P1:23 P1:24...
Page 21
Installation Manual Chapter 1: Connection to central unit 1 - 16 Salwico CS3000 Terminal P2 Ark-2 and LPK-2 Description Function Voltage Current Terminal Inputs : 35 VDC = 10 mA if P2:1 in max = 24 VDC (opto-isolated) Active input:...
Page 22
Installation Manual Chapter 1: Connection to central unit 1 - 17 Salwico CS3000 Terminal P3 RS232K-2 and KPK-2 Description Function Voltage Current Terminal RS232 port P3:1 Rx D P3:2 P3:3 P3:4 P3:5 RS485 port P3:6 Channel 1 P3:7 Channel 1 -...
Page 23
Installation Manual Chapter 1: Connection to central unit 1 - 18 Salwico CS3000 Terminal P4 INK-2 and UTK-2 Description Function Voltage Current Terminal Inputs : 35 VDC = 10 mA if P4:1 in max = 24 VDC (opto-isolated) Active input:...
Page 24
Installation Manual Chapter 1: Connection to central unit 1 - 19 Salwico CS3000 Terminal P5 INK-2 Description Function Voltage Current Terminal Inputs : 35 VDC = 10 mA if P5:1 in max = 24 VDC Active input: P5:2 min 1,3 mA...
Page 25
Installation Manual Chapter 1: Connection to central unit 1 - 20 Salwico CS3000 Terminal P6 UTK-2 Description Function Voltage Current Terminal Programmable outputs : 35 VDC : 50 mA P6:1 ut max ut max (opto-isolated) P6:2 P6:3 P6:4 P6:5 P6:6...
Page 26
Installation Manual Chapter 1: Connection to central unit 1 - 21 Salwico CS3000 Terminal S1 SPK-2 Description Function Voltage Current Terminal Detectors and push buttons Out + S1:1 Loop 1 Out - S1:2 In + S1:3 In - S1:4 Loop 2...
Installation Manual Chapter 1: Connection to control unit 1 - 22 Salwico CS3000 Connection to control unit Internal connection of control unit The IKK-4 board is installed and connected to the central unit panel CSM-3150 at delivery., see figure below.
Installation Manual Chapter 1: Connection to control unit 1 - 23 Salwico CS3000 Terminal layout IKK-4 The figure below shows the layout of the terminal on the IKK-4 board. The terminal is described in detail on the next pages. Figure 1-3. Terminal layout, control unit.
Installation Manual Chapter 1: Connection to control unit 1 - 24 Salwico CS3000 Terminal description IKK-4 The specification may be subject to changes without notice. Description Function Voltage Current Terminal Power supply 24 VDC U: 24 VDC RS485 Option Inputs...
Page 30
Installation Manual Chapter 1: Connection to control unit 1 - 25 Salwico CS3000 Description Function Voltage Current Terminal RS232 Port 1 RS232 Port 2 (Option) S1:31 System communication Loop 1 System communication Loop 2...
Installation Manual Chapter 2: Loops 2 - 1 Salwico CS3000 Chapter 2: Verification The definition of the loop must be performed by a person with a good knowledge of the CS3000 fire system. The operator must have the authority to work on access level 4.
Page 32
Installation Manual Chapter 2: Loops 2 - 2 Salwico CS3000 7. Verify that the correct number of section units and the correct type of section units are installed in the correct place. The system will provided you with the requested information if you use the Section unit status list. If a section unit is missing, see Wrong number of section units later on in this chapter.
Installation Manual Chapter 2: Loops 2 - 3 Salwico CS3000 9. Restart the system and wait for about five minutes before data is relevant in the system. 10. Verify the section addresses again, repeat point 7. 11. One loop is now verified and tested. Continue with the next loop. Repeat this procedure for all loops.
Page 34
Installation Manual Chapter 2: Loops 2 - 4 Salwico CS3000 If a limited number of section units do not answer, the problem may depend on one of the causes listed below. When the correct number of section units is installed, return to Loops, point 7.
Installation Manual Chapter 2: Loops 2 - 5 Salwico CS3000 Information about analogue values All information about the analogue values for each type of section unit is listed in the following tables. Detectors and manual call points The listed analogue values for detectors and manual call points include alarm levels, fault condition levels and normal values for all analogue channels.
Page 36
Installation Manual Chapter 2: Loops 2 - 6 Salwico CS3000 Other section units All information about analogue values for other types of units, units not detecting fire conditions, are listed below. Analogue values for other loop units Loop Unit Channel...
Installation Manual Chapter 2: Loops 2 - 7 Salwico CS3000 Control unit At power-up the text CS3000 CONTROL UNIT, the date and the time are displayed on the display if all the units have been installed correctly. A fault code is otherwise displayed on the operating panel, the fault indication is flashing and the internal buzzer is sounding.
Installation Manual Chapter 2: Loops 2 - 8 Salwico CS3000 Mute faults The internal buzzer is temporarily silenced when the door is opened. • Mute the fault. The fault indication stops flashing and turn over to steady yellow. The fault is put on a fault list and the next fault is displayed, if there are more faults in the system, otherwise the system returns to its previous state.
Installation Manual Chapter 3: Section description 3 - 2 Salwico CS3000 Chapter 3: System description Loop description A loop is defined as the cable connecting the central unit and the section units, including the section units. The two-core cable is used both for power supply to the section units and as a communication link between the loop processor and the section units.
Installation Manual Chapter 3: Section description 3 - 3 Salwico CS3000 sequence is immediately interrupted. The value is verified according to the verification algorithm and the result is reported to the user/operator. Functions The functions of the system are grouped into different levels and each level is opened with an access code.
”Address list/test report for Consilium Loop Units” one for each loop in the system. Part C (Central status) is also a check list but it deals with the status of the central unit.
10. Fax each signed protocol in one copy to Consilium authorised representative and one copy to Consilium Marine, Gothenburg, Sweden. 11. When all loops are tested and all protocols are signed, a Consilium service engineer can be asked to come for the final control and adjustment of the...
1. All control and indication functions must be connected to relay outputs. Outputs and inputs according to Consilium terminal drawings and ”Installations Manual Salwico CS3000” 2. All loops shall be connected to the central according to Consilium terminal drawings. 3. All deviations from above criteria’s causes delay-time and will be invoiced.
Page 44
Installation Manual Appendix A Salwico CS3000 Appendix A The Address List/Test Reports...
Address List / Test Report Loop no. (1/2) ....for Consilium Marine CS4000 Fire Alarm Loop Units Example o o o o o o o o o o o o o o Not OK o o o o o o o o o...
Page 46
Address List / Test Report Loop no. (2/2) ....for Consilium Marine CS4000 Fire Alarm Loop Units Example o o o o o o o o o o o o o o Not OK o o o o o o o...
Page 47
Installation Manual Appendix B Salwico CS3000 Appendix B Connections for Consilium Marine loop units...
Page 48
ÇConsilium Marine Connection of loop units Detectors Manual call points NS-AOS NS-ACP NS-AIS NS-ACP IP55 NS-AH/AIS NS-ACPWP NS-AOHS NS-AH/CS NS-AIHS NS-AUV Short circuit isolator Timer NS-SCI NS-TIMAC Loop IN Loop OUT Address units NS-AIN1/ID3 NS-AIN1/ID2 Conventional detectors Safe area Loop IN...
Page 49
ÇConsilium Marine Connection of loop units Address units AE-2 AE-2K AE-2K/I AE-2E ID Switch Detectors Evolution type detectors RDJ-2 RDJ-2T RDO-2 TDT-2 1(+) Loop in Loop out HA100-HA110 OA100-140 6(-) IA100-140 3(-) WITH BASES: UB-1, UB-2 SPB-ADAPT 3 mA remote...
Page 50
Installation Manual Fault codes Appendix C: Fault codes The word FAULT is displayed on the first line of the display together with a fault code followed by the section number and the address for the section unit causing the problem, if the system has this information. Additional text is displayed on line two, if provided.
Page 51
Installation Manual Fault codes Wrong definition of number of Compare the installation with 8 Additional section unit(s) * section units. the drawings. Contact our service department. Section unit connections faulty. Connect the unit correctly. Bad communication with one or Exchange the section unit if the 21 Bad answer (Abnormal condition) several section units, could be...
Page 52
Installation Manual Fault codes Overlapping address intervals. Set a valid address interval. 43 Wrong address interval End-address of the interval is Set a valid address interval. lower then the start-address. 44 Illegal address Faulty section unit. Exchange the section unit. Output not configured in DEF-P Check DEF-P 51 Loop output missing...
Page 53
Installation Manual Fault codes Replace unit 89 No autoalarm Unable to use autoalarm Optical smoke detector: Clean Detector head is polluted. 90 Polluted detector the detector head according to (Abnormal condition) recommendations. Ion smoke detector: Exchange the detector. Hardware is faulty Exchange the unit 91 Hardware fault 92 Not resettable...
Page 54
Installation Manual Fault codes Short circuit between the Attend to the problem. 126 Short circuit on prim. positive and the negative Side connector on the primary side. 127 Short circuit on sec. Short circuit between the Attend to the problem. positive and the negative Side connector on the secondary side.
Page 55
Installation Manual Fault codes Warning signal if a disconnected Only information. 165 Disconnected detector in detector reaches its alarm level alarm Damper/door in wrong position. Check for obstruction. 166 Damper /Door should have been opened Damper/door in wrong position. Check for obstruction. 167 Damper /Door should have been closed The detector has a faulty sensor...
Page 56
Installation Manual Fault codes The battery charger is unable to Check the battery charger and 185 Loss of capacity to charge charge the battery. the battery. battery Fault from input. Check cable and/or external 186 External Fault unit. Check the offending units Set correct addresses for the 187 Double address on loop against drawings.
Page 57
Installation Manual Fault codes Cable break No section units are answering. - The cable is broken before the first section unit if no answer is received on a single fed loop. - The cable is broken before the first section unit and after the last section unit the if the loop is a double fed loop.
Page 58
Installation Manual Fault codes Fuses Check the fuses on the boards included in the system. The fuses are mounted on the front panels on the following boards: ARK-2, GSK-2, INK-2, KPK-4, LPK-2, RS232K-2, SPK-2 and UTK-2. The fuses to the IKK-4 are mounted on the board itself.
Page 59
Appendix D: Installation and operation addendum Installation and Operation Addendum for Salwico CS3000 and CS3004 as U.S. Coast Guard Approved System The fire detection system must be installed and configured in accordance with Subpart 161.002 and Subchapter J of Title 46 of the U.S. Code of Federal Regulations, and with the 1993 or later version of NFPA 72.
Page 60
Appendix E CS3000 Appendix E: Component list for USCG approved systems Approved Component List for Salwico CS3000 or CS3004 systems as an U.S. Coast Guard approved system. Components Also for Locations Requiring Exceptional Degree of Protection Central panels, repeaters, bells and power supply CS3000, Fire Alarm Panel incl.