Fire Alarm System
Salwico CS3000
Service manual
Ver. 6
çConsilium

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Salwico CS3000 and is the answer not in the manual?

Questions and answers

Summary of Contents for Consilium Salwico CS3000

  • Page 1 Fire Alarm System Salwico CS3000 Service manual Ver. 6 çConsilium...
  • Page 2 The contents of this document are subject to revision without notice due to continued progress in methodology, design and manufacturing. Consilium assumes no legal responsibility for any error or damage resulting from the usage of this document. Edition 5, 09 1 E, August 2009.
  • Page 3: Table Of Contents

    Appendix A. DIP switch settings ............... A-1 Appendix B. Fault codes CS3000 version 4 ........B-1 Appendix C. Fault codes CS3000 version 6 ........C-1 Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 1995, Consilium Marine AB...
  • Page 4: About This Manual

    CS3000 Version 4 and Fault Codes CS3000 Version 6 appendixes respectively. For a more detailed description of the system refer to the CS3000 Reference Manual. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 1995, Consilium Marine AB...
  • Page 5: Service Mode

    SERVICE function. The short circuit isolators remain bypassed until you activate them again. • Press F4 (MENU) until SERVICE is displayed on line 4. • Press F1 (SERVICE). Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 1995, Consilium Marine AB...
  • Page 6: Input/Output Board

    500 mAT 5x20 mm Not supervised F4: Power supply ext. device 315 mAT 5x20 mm Not supervised F5: Power supply 315 mAT 5x20 mm Not supervised Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 1995, Consilium Marine AB...
  • Page 7 Service Manual CS3000 Chapter 2: Input/Output board IKK-4 The circuit board of the control unit Function Block diagram Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 1995, Consilium Marine AB...
  • Page 8 A fused and fault supervised output for power supply to an external device. 13. Opto-isolated inputs Four opto-isolated transient protected external inputs. 14. Opto-isolated outputs Four transistor outputs. Deactivated at hang-ups in the programme execution. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 1995, Consilium Marine AB...
  • Page 9 Current consumption: I in nom : 15 mA I in max : 40 mA. Outputs: 4 opto-isolated sourcing outputs Inputs: 4 opto- isolated inputs, active high Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 1995, Consilium Marine AB...
  • Page 10: Loop Processor Board

    #1. No 7 (yellow) when lit: fault in loop #2. No 8 (red) when lit: fire alarm in loop #2. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 11 1. Disconnect the power by removing the fuse. WARNING! The power must be disconnected before the board is removed. 2. Remove the board and replace it with the new board. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 12 The circuit boards of the central unit Function Block diagram Model 1 & Model 2 NB! In the diagram blocks 8 - 14 are doubled, one set for each detector loop. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 13 15. Buses The control signal bus contains signals to control the reading and writing of devices connected to the address bus and the data bus. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 14 The processor controls the loops and communicates with the LPK via the RS485 channel of the back plane. The whole board is galvanically isolated from the CS3000 rack. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 15 Separating and filtering out IDA/NOSE communication from the DC supply voltage on the loop. Loop: Line modem Sending and receiving IDA/NOSE communication. Communication with the processor via serial channel. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 16 Normally strapped. Normally strapped. JP3 and JP4 can be used to enhance reception of loop communication in case of loops with communication problems. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 17 : 120 mA (no loop units connected) in nom 1300 mA in max Output voltage: : 32 - 34 VDC Output current: : 300 mA/loop ut max Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 18: Alarm Processor Board

    The addresses of the other LPK-2, if installed in the system, are set according to the definition in the Definition program. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 19 2. To avoid activation of Bells, remove fuses F5-F10 on ARK-2. WARNING! The power must be disconnected before the board is removed. 3. Remove the board and replace it with the new board. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 20 ADDRESS SWITCH SYSTEM SYSTEM SWITCH COM. LOOP LOOP 2 TX/RX (CSM/LPK) ADDRESS/DATA/CONTROL REAL TIME DATA/ADDRESS BUFFERS CLOCK BACK PLANE SIGNALS BASIC BLOCK ALARM RELAY OUTPUTS Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 21 Two relay outputs for connection to the fire brigade. The alarm relay is programmable and the other relay is activated when there are not muted faults in the system. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 22 : 24 VDC (-20% - + 25%). Current consumption: : 80 mA in nom : 120 mA. in max Outputs: 2 relays, 480 mA, 125 V Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 23 Alarm bell output 3+ Alarm bell output 3- F11 Relay output RL1 Relay output RL2 F13 Relay output RL3 GA-output Salwico ARK-2 Fuse rating: 2 AT 5x20 mm Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 24 The power must be disconnected before the board is removed. 2. Remove the board and replace it with the new board. 3. Start up the central by inserting F3+F4 and F5+F6 in that order. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 25 G A INTE RM . INPUT SW IT CH SW IT CH EXT. FUSE FA ULT INPUT BA SIC A LA RM O PTO ISO L. uP BUS Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 26 Input for indication of fuse fault in external devices. 15. BASIC-ALARM input 16. Opto-isolated inputs Four opto-isolated inputs for external signals. 17. Micro processor bus Connection of micro processor bus to the LPK. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 27 Two open-collector outputs, PTC-protected, one programmable and one activated at not muted fault in the central unit, U : 24 V, I : 100 mA max. sink max. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 28 The power must be disconnected before the board is removed. 2. Remove the board and replace it with the new board. 3. Start up the central by inserting F3+F4 and F5+F6 in that order. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 29 4 OPTO- 4 OPTO- 4 OPTO- 4 OPTO- 4 OPTO- 4 OPTO- ISOLATED ISOLATED ISOLATED ISOLATED ISOLATED ISOLATED INPUT INPUTS INPUTS INPUTS INPUTS INPUTS INPUT CONNECTOR Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 30 The inputs are protected by transient suppressors. Each input is equipped with an LED that is lit when the input is active. These LEDs are not visible from the front panel. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 31 Input current: : 10 mA at U = 24 V. Activated input: : 1.3 mA in min Deactivated input: : 0.1 mA in max Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 32 The power must be disconnected before the board is removed. 2. Remove the board and replace it with the new board. 3. Start up the central by inserting F3+F4 and F5+F6 in that order. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 33 4 OPTO- 4 OPTO- 4 OPTO- 4 OPTO- 4 OPTO- 4 OPTO- ISOLATED ISOLATED ISOLATED ISOLATED ISOLATED ISOLATED OUTPUTS OUTPUTS OUTPUTS OUTPUTS OUTPUTS OUTPUTS OUTPUT CONNECTOR Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 34 Output current: : 50 mA out max Voltage drop: : 1.2 VDC @ 50 mA Leakage current: : 3 mA @ 70 C out max Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 35 The jumpers are factory set (as in the picture) for source output on all lines. SOURCE SINK Output group configuration. 4 outputs per group Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 36: Interface Board

    Setting the addresses The address of the first GSK-2 board is set to binary 1, the second GSK-2 board is set to binary 2, etc. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 37 1. Disconnect the power by removing the fuse. WARNING! The power must be disconnected before the board is removed. 2. Remove the board and replace it with the new board. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 38 D/A CONV. FIRE,FAULT TEST AND INHIBIT AND STATUS BARRIER LOGIC ANALOG DETECTION INPUTS SECTION 4 FIRE,FAULT MONITOR TEST AND INHIBIT AND STATUS BARRIER LOGIC DETECTION Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 39 Each section can be electrical isolated from the central unit by a double relay. 10. Barrier Each section output is protected against transients and hf-interference. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 40 : 24 VDC (-20% -- + 25%). Output current: : 2.4 mA at U = 24 V. Fire alarm: : 17 mA out min Broken connection: : 0.8 mA out max Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 41 #9 are set. Bit #5 is set with SW1-4. The address of each RS232K-2 board is set according to the definition in the Definition program. For more information see Appendix A. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 42 The power must be disconnected before the board is removed. 2. Remove the board and replace it with the new board. 3. Start up the central by inserting F3+F4 and F5+F6 in that order. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 43 CONVERTER FUSE FAULT SUPERVISION POWER FAULT ADDRESS BUS CONTROL ADDRESS LOGIC BUFFER DATA BUS DATA BUFFER STATUS REGISTER STATUS REGISTER UART UART UART UART INDICATOR Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 44 14. Line protection The line protector includes resistors for level definition of the line when not in use. Line protection with zener diodes and varistors. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 45 Input power: : 24 VDC (-20% - +25%) Current consumption: : 10 mA @ 24 V in nom : 40 mA @ 24 V in max Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 46 Setting the address The address of the board is set with a DIP-switch (SW1), two switches. The recommended address and DIP-switch setting are provided in Appendix A. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 47 The power must be disconnected before the board is removed. 2. Remove the board and replace it with the new board. 3. Start up the central by inserting F3+F4 and F5+F6 in that order. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 48 Service manual CS3000 Chapter 3: Interface board KPK-2 3-39 The circuit boards of the central unit Function Block diagram Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 49 12. Board address Selects the board address. 13. RS232 D-SUB HEADER Male 9-pin D-sub header on the front panel with IBM PC/AT pin-standard. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 50 Input voltage: : 24 VDC (-20% - +25%) Current consumption: : 25 mA @ 24 V in nom : 25 mA @ 24 V in max Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 51 Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 52 14, each 6 TE width (30.1 mm) Ambient temperature: -10°C -- +70°C Humidity: 96 % Rh Input power: : 24 VDC (-20% -- + 25%) Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 53: Power Unit

    Colour Function Green Mains voltage Green Emergency voltage Green: Rapid charge Yellow General fault indication Yellow Battery fault Yellow Mains/emergency fault Yellow Earth fault indication Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R2 2002-08-14 BM © 1995, Consilium Marine AB...
  • Page 54 4 AT 6,3 x 32 mm Net fuse 4 AT 6,3 x 32 mm WARNING! When starting up the central first insert fuses F3+F4, and then F5+F6 in that order. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R2 2002-08-14 BM © 1995, Consilium Marine AB...
  • Page 55 The charging current can be set between 0-10 A and the charging voltage can be set between 21 - 34 VDC. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R2 2002-08-14 BM © 1995, Consilium Marine AB...
  • Page 56 Definition program . INK-2 Address Hex. RS232K-2 board 1 Address Hex. RS232K-2 board 2 Address Hex. UTK-2 board 1 Address Hex. UTK-2 board 2 Address Hex. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 1995, Consilium Marine AB...
  • Page 57 UTK-2 board 4 Address Hex. UTK-2 board 5 Address Hex. UTK-2 board 6 Address Hex. KPK-4 board 1 Address Hex. KPK-4 board 2 Address Hex. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 1995, Consilium Marine AB...
  • Page 58 Mend the cable. LPK-2 has a hardware fault. Exchange the board. Wrong definition of number of Check the specification and repeater panels. redefine the system. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 59 Remedy Wrong definition of number of Compare the installation with the section units. drawings. Redefine the system. Section unit connections faulty. Connect the unit correctly. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 60 Exchange the section unit. Wrong software in CS3000. Exchange the software. Wrong type of detector has been Install the correct type of detector. installed. Restart the system. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 61 MEMORY CKECKSUM ERROR Data in memoryhas been unintensionally damaged. Cause Remedy Error in RAM or EPROM. Restart. If the fault returns exchange the unit. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 62 Remedy A fuse is blown. In the display is Exchange the fuse. See Fuses at shown which fuse is blown. the end of this chapter. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 63 Battery fuse blown, cable break or bad battery in central unit. 101 ALARM FUNCTION FAILURE Cause Remedy The alarm function in the Exchange the detector. detector does not work. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 64 BREAK (121), since the loop is broken. The short circuit faults must always be reset before other faults. Cause Remedy Short circuit on detector loop See Short circuit at the end of this chapter. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 65 Too low system voltage from the Test the rectifier and measure the power unit. voltage. Too low voltage: → Exchange the rectifier. Normal voltage: → Exchange the IOK-4 board. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 66 Too high system voltage from Test the rectifier and measure the power unit. voltage. Too high voltage: → Exchange the rectifier. Normal voltage: → Exchange the IOK-4 board. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 67 Continue to divide the cable into halves until you have found the earth fault. If you are using a multimeter use the diode tester range. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 2002, Consilium Marine AB...
  • Page 68 Not supervised IKK-4 F5: Power supply 315 mAT 5x20 mm * The central unit is not working properly. Indicator No. 1 (green) is not lit. Document no.: S-4-007.875/E Prepared: 1995-03-17 Fia Revision: R4 2004-03-15 BM © 1995, Consilium Marine AB...
  • Page 69 Mend the cable. LPK-2 has a hardware fault. Exchange the board. Wrong definition of number of repeater Check the specification and panels. redefine the system. Document no.: S-4-007.875/E Prepared: 2002-10-01 BM Revision: R5 2004-04-07 BM © 2002, Consilium Marine AB...
  • Page 70 Loop unit connections faulty. Connect the unit correctly. LOOP MISSING DEF. DATA Cause Remedy The loop has not been defined properly at Redefine the loop. the installation. Document no.: S-4-007.875/E Prepared: 2002-10-01 BM Revision: R5 2004-04-07 BM © 2002, Consilium Marine AB...
  • Page 71 APPEARS, code (121). at the end of this chapter. WRONG IDA STATUS Incorrect answer from the loop unit. Cause Remedy Loop unit faulty Exchange the loop unit. Document no.: S-4-007.875/E Prepared: 2002-10-01 BM Revision: R5 2004-04-07 BM © 2002, Consilium Marine AB...
  • Page 72 Cause Remedy Two loop units have the same address. Check the addresses of the units and set correct adresses. Loop unit faulty. Exchange the unit. Document no.: S-4-007.875/E Prepared: 2002-10-01 BM Revision: R5 2004-04-07 BM © 2002, Consilium Marine AB...
  • Page 73 Exchange the loop unit. LOOP OUTPUT MISSING Cause Remedy The loop unit has no active outputs. Error Download new set-up data. in the site set-up. Document no.: S-4-007.875/E Prepared: 2002-10-01 BM Revision: R5 2004-04-07 BM © 2002, Consilium Marine AB...
  • Page 74 Mend the cable. See Cable break at the end of this chapter. Example: FAULT (81) 1 POWER MAINS FAULT Mains power failure in the power unit. Document no.: S-4-007.875/E Prepared: 2002-10-01 BM Revision: R5 2004-04-07 BM © 2002, Consilium Marine AB...
  • Page 75 A fuse blown or a cable break in external alarm device 9. FAULT (93) BATTERY FUSE/CABLE FAULT Battery fuse blown, cable break or bad battery in central unit. Document no.: S-4-007.875/E Prepared: 2002-10-01 BM Revision: R5 2004-04-07 BM © 2002, Consilium Marine AB...
  • Page 76 This message can only emanate from the central unit itself. FAULT (121) SEC 1 CABLE BREAK Cable break in detector loop. See also (125). Document no.: S-4-007.875/E Prepared: 2002-10-01 BM Revision: R5 2004-04-07 BM © 2002, Consilium Marine AB...
  • Page 77 Earth fault between positive terminal and See Earth fault at the end of this earth. chapter. FAULT (141) POWER EARTH FAULT + Earth fault to plus from the power unit. Document no.: S-4-007.875/E Prepared: 2002-10-01 BM Revision: R5 2004-04-07 BM © 2002, Consilium Marine AB...
  • Page 78 Check the door. instruction to close it was sent. 163 OPEN DOOR SUBLOOP BREAK Cause Remedy Cable break between module and open Mend the cable. door sensor. Document no.: S-4-007.875/E Prepared: 2002-10-01 BM Revision: R5 2004-04-07 BM © 2002, Consilium Marine AB...
  • Page 79 There is a cable break on input 2. Check the cable. 173 DOOR FEEDBACK Cause Remedy There is no response from the door- Check the door-holder relay and its holding relay. cable. Document no.: S-4-007.875/E Prepared: 2002-10-01 BM Revision: R5 2004-04-07 BM © 2002, Consilium Marine AB...
  • Page 80 179 UNABLE TO DETECT SHORT CIRCUIT Cause Remedy Unable to detect short circuit. Exchange loop-PCB. 180 SPRINKLER VALVE CLOSED Cause Remedy Sprinkler valve closed. Check why it is closed. Document no.: S-4-007.875/E Prepared: 2002-10-01 BM Revision: R5 2004-04-07 BM © 2002, Consilium Marine AB...
  • Page 81 Check cable and/or external unit. 187 DOUBLE ADDRESS ON LOOP Cause Remedy Check the offending units against Set correct addresses for the units, drawings. with the DIP-switches. Document no.: S-4-007.875/E Prepared: 2002-10-01 BM Revision: R5 2004-04-07 BM © 2002, Consilium Marine AB...
  • Page 82 Continue dividing the cable into halves until the earth fault has been found. If you are using a multimeter use the diode tester range. Document no.: S-4-007.875/E Prepared: 2002-10-01 BM Revision: R5 2004-04-07 BM © 2002, Consilium Marine AB...
  • Page 83 GPK-4 500 mAT I/O-board IKK-4 IKK-4 board 100 mAT (IKK-4) IKK-4 Output devices 500 mAT IKK-4 Voltage output 315 mAT IKK-4 Voltage output 315 mAT Document no.: S-4-007.875/E Prepared: 2002-10-01 BM Revision: R5 2004-04-07 BM © 2002, Consilium Marine AB...