Insufficient heat transfer due to lime scale or
contamination in the CH boiler on the tap water
side.
9.3.8
CH installation stays warm unwanted
Possible causes:
Room thermostat/weather dependent regulation
faulty or short circuited.
No 
CH installation is heated due to Tap comfort.
The service display regularly shows code 7.
9.3.9
A-label pump LED flashes intermittently red/green
Possible causes:
Too high or too low mains voltage.
No 
Pump temperature is too high.
9.3.10 A-label pump LED flashes red
Possible causes:
Pump stopped.
Daikin Europe NV
Yes  Remove lime scale or rinse the CH boiler on the tap water side.
Solution/cause:
Check the wiring.
Check OpenTherm and On/off connection of the unit.
Yes 
Replace the thermostat.
Replace the weather-dependent regulation.
Unwanted circulation in the CH circuit due to thermosiphon effect or second pump in
Yes 
the CH circuit. Install a check valve in case of thermosiphon effect or a two-way
valve in case of a second pump.
Solution:
Yes  Check the mains voltage.
Yes  Check the water and ambient temperature.
Solution:
Reset the pump by switching off the unit by pressing the on/off button for at least 20
seconds
(attention: if the pump has been set to continuous, the pump can only
Yes 
be reset by pulling the plug from the socket).
Replace the pump.
51