Bodine ELI-S-400-2HR Installation And Operation Instruction Manual

Sinewave inverter

Advertisement

ELI-S-400 LFP
ELI-S-400-2HR
SINEWAVE INVERTER
Installation and Operation Instructions
ELI SERIES EMERGENCY LIGHTING INVERTERS

! IMPORTANT SAFEGUARDS !

READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1.
Do not use outdoors.
2. Do not let power supply cords touch hot surfaces.
3. This product is suitable for use in damp locations where the ambient temperature is 20ºC minimum,
30ºC maximum. Product is not suitable for heated air outlets and wet or hazardous locations. DO
NOT INSTALL NEAR GAS OR ELECTRIC HEATERS.
4. Equipment should be mounted securely in locations and at heights where it will not be readily
subjected to tampering by unauthorized personnel.
5. The use of accessory equipment and replacement parts not recommended by the manufacturer may
cause an unsafe condition.
6. Do not use this equipment for other than its intended purpose.
7.
The AC voltage rating of this equipment is 120 or 277 VAC. Do not connect equipment to any other
voltage.
8. This device complies with Part 15 of the FCC Rules. Operation is subject to the following two
conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference that may cause undesired operation.
Consumer Information:
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant
to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance
with the instruction manual, may cause harmful interference to radio communications. Operation of
this equipment in a residential area is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
! IMPORTANT ! - PLEASE TAKE NOTE BEFORE THE INSTALLATION:
You must determine how the connected emergency lighting fixtures are to operate; normally-on (unswitched
and always energized), normally-off (only energized during a power failure), or switched on/off. Wire
according to the appropriate wiring diagram given below. Consult factory for special wiring diagrams.
Ensure that ALL combined/connected Emergency lighting loads are less than 800W in normal mode and are
capable of being dimmed down to 400VA from an industry standard 0-10V source in Emergency mode.
ELI-S-400 LFP and ELI-S-400 2HR WILL ONLY deliver 400VA maximum into the connected lighting load. This is
accomplished by automatically dimming the connected emergency lighting loads down to the product output
power rating.
THIS PRODUCT INCLUDES RECHARGEABLE LITHIUM BATTERIES.
THE BATTERIES MUST BE RECYCLED OR DISPOSED OF PROPERLY.
Li - ion
Collierville, TN USA • Tech Support 888-263-4638 • Fax 901-853-5009 • www.bodine.com
SAVE THESE INSTRUCTIONS
2/3/2023
Bodine © 2023 Signify Holding. All rights reserved.
442296136811
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY
PRECAUTIONS SHOULD ALWAYS BE FOLLOWED,
INCLUDING THE FOLLOWING:
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ELI-S-400-2HR and is the answer not in the manual?

Questions and answers

Summary of Contents for Bodine ELI-S-400-2HR

  • Page 1 THIS PRODUCT INCLUDES RECHARGEABLE LITHIUM BATTERIES. THE BATTERIES MUST BE RECYCLED OR DISPOSED OF PROPERLY. Li - ion 2/3/2023 Bodine © 2023 Signify Holding. All rights reserved. Collierville, TN USA • Tech Support 888-263-4638 • Fax 901-853-5009 • www.bodine.com 442296136811...
  • Page 2 ELI-S-400 LFP 120/277Vac 120/277Vac 400 VA 800 W Minimum of 90 minutes ELI-S-400-2HR 120/277Vac 120/277Vac 400 VA 800 W Minimum of 120 minutes * NOTE: AC Input Power to an LED or Fluorescent Driver/Ballast is always more than the output power. Furthermore, dimming drivers are less efficient at reduced power.
  • Page 3 STEP #2 BATTERY INSTALLATION AND CABLE CONNECTION This product is provided with four sealed Lithium ion batteries. Only the batteries supplied by the inverter manufacturer should be used. Install the batteries as shown, referring to Illustrations 2A and 2B. With the unit secured to the mounting surface, begin installation by sliding the batteries into the enclosure. Connect the battery cables using the supplied hardware.
  • Page 4 Dimming. When AC power is restored, the unit returns to normal charging mode. The ELI-S-400 LFP operates the emergency lighting load for a minimum of 90 minutes and ELI-S-400-2HR operates the emergency lighting load for a minimum of 120 minutes.
  • Page 5 MAINTENANCE & TROUBLESHOOTING WARNING: Always turn off SW-1(first), then turn off AC power to the equipment inside the case before servicing. ! REFER ANY SERVICING TO QUALIFIED PERSONNEL ! Servicing should be performed only by qualified service technicians. Use only manufacturer supplied replacement parts.
  • Page 6 1x Littlefuse 0312030 PRT00400 1 Required ELI-S-400-2HR Battery Maintenance: The batteries supplied with this equipment require no maintenance. However, the inverter should be tested periodically, and batteries replaced whenever they will no longer operate the connected fixtures for the rated run-time. The batteries supplied have a life expectancy of four years when used in normal ambient temperature of 72 degrees F.
  • Page 7 Non-DIMMABLE EMERGENCY LIGHTING SYSTEM TOTAL POWER ANY QUANTITY SUPPORTED BY THE BRANCH CIRCUIT =400W Norm/Emer Normal only Normal only Norm/Emer Luminaire Luminaire Luminaire Luminaire Norm/Emer Normal only Norm/Emer Normal only Luminaire Luminaire Luminaire Luminaire 120 or 277 VAC INVERTER Wall Switch Out HOT SW HOT 120 or 277 VAC...

This manual is also suitable for:

Eli-s-400 lfp

Table of Contents

Save PDF