Bodine ELI Series Installation And Operation Instructions Manual

Bodine ELI Series Installation And Operation Instructions Manual

Emergency lighting inverter with auto-dimming feature

Advertisement

Quick Links

ELI-S-100
WITH AUTO-DIMMING FEATURE
Installation and Operation Instructions
ELI SERIES EMERGENCY LIGHTING INVERTERS
! IMPORTANT SAFEGUARDS !
READ AND FOLLOW ALL SAFETY INSTRUCTIONS
1. Caution:
• High voltage will be present on the output wires and terminals if batteries are installed and inverter
connector is joined or if AC power is supplied to the switched and unswitched terminal.
• Ensure input and output primary wiring connections are made to the proper terminals. Damage to product
may occur if miswired.
• Ensure load voltage requirements (120 or 277 Vac) match the output ratings of this product or damage to
the load devices may occur.
2. This product is suitable for use in dry and damp locations where the ambient temperature is 0°C through
40°C, depending on load. See output ratings on product label for details. This product is not suitable for
heated air outlets and wet or hazardous locations.
3. Make sure all connections are in accordance with the National Electrical Code or Canadian Electrical Code
and any local regulations.
4. To reduce the risk of electric shock, disconnect both the normal and emergency power supplies and the
inverter connector of the emergency lighting inverter before servicing.
5. Do not install near gas or electric heaters.
6. An unswitched AC power source is required. The AC voltage rating of this equipment is specified on the
product label. Do not connect equipment to any other voltage.
7. Equipment should be mounted securely in locations and at heights where it will not be readily subjected to
tampering by unauthorized personnel.
8. The use of accessory equipment and replacement parts not recommended by the manufacturer may cause an
unsafe condition.
9. Do not use this equipment for other than its intended purposes.
10. The battery is field replaceable. Contact manufacturer for information on replacement. Use caution when
replacing battery. Dispose of the battery properly. Do not incinerate.
236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-853-5009 • www.bodine.com
SAVE THESE INSTRUCTIONS
THIS PRODUCT INCLUDES RECHARGEABLE LEAD-ACID BATTERIES.
THE BATTERIES MUST BE RECYCLED OR DISPOSED OF PROPERLY.
Bodine © 2018 Signify Holding. All rights reserved.
WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY
PRECAUTIONS SHOULD ALWAYS BE FOLLOWED,
INCLUDING THE FOLLOWING:
Pb
11/27/18
81000092

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ELI Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Bodine ELI Series

  • Page 1 THIS PRODUCT INCLUDES RECHARGEABLE LEAD-ACID BATTERIES. THE BATTERIES MUST BE RECYCLED OR DISPOSED OF PROPERLY. 11/27/18 Bodine © 2018 Signify Holding. All rights reserved. 236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-853-5009 • www.bodine.com 81000092...
  • Page 2 INSTALLATION WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON THE AC OUTPUT LEADS (HOT AND NEUTRAL) PRIOR TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN. JOIN INVERTER CONNECTOR INSIDE THE CASE AFTER INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED. NOTE: Make sure the inverter connector is closed before screwing the front cover to the case.
  • Page 3 INSTALLATION ILLUSTRATION 2 PRIMARY WIRING CONNECTIONS UnSwHot SwHot COM GND OutHot OutCom LOAD NEUTRAL OUTPUT CONNECTIONS LOAD HOT SAFETY GROUND NEUTRAL AC POWER SOURCE INPUT SWITCH LINE HOT CONSTANT HOT ENCLOSURE GROUNDING CAUTION: • Unswitched and switched AC power must be fed from the same branch circuit. •...
  • Page 4 The charging indicator light should be illuminated once unswitched AC power is restored. Use only Bodine part number PRT00133 as replacement batteries. Utilisez uniquement la référence Bodine PRT00133 en tant que remplacement de la batterie.
  • Page 5 INSTALLATION STEP #6 JOIN THE INVERTER CONNECTOR & APPLY POWER > After installation is complete, apply AC power and join the inverter connector inside the case then screw the front cover to the case. Note: > The inverter has a safety lockout feature that pervents AC output in emergency mode until AC mains power is connected and then lost.
  • Page 6 INSTALLATION Battery: The battery supplied with this equipment requires no maintenance. However, it should be tested periodically and replaced whenever it will no longer operate the connected fixtures for the duration of a 90-minute test. The battery supplied has a life expectancy of four (4) years when used in normal ambient temperature of 72°F. Fuse: The fuse contained within this product is field replaceable.

This manual is also suitable for:

Eli-s-100

Table of Contents