7.APPENDIX

7.3 Comparison table of refrigerant saturation temperature

Pressure
0
(MPa )
Temperature
-51.3
(R410A)( )
Temperature
-52.5
(R32)( )
Pressure
2.5
(MPa )
Temperature
43
(R410A)( )
Temperature
42
(R32)( )
0.3
0.5
0.8
-20
-9
4
-20
-9
3.5
2.8
3
3.3
47
51
55
46.5 49.5 53.5
46
1
1.3
1.5
11
19
24
10
18
23
3.5
3.8
4
57
61
64
56
60
62
1.8
2
2.3
31
35
39
29.5 33.3 38.7
4.5
5
5.5
70
74
80
67.5 72.5 77.4