Do not operate the compressor without enough system
charge to maintain at least 55 psig (3.8 bar) suction
pressure. Do not operate with a restricted suction or
liquid line. Do not operate with the low pressure cut-out
disabled.
Allowing suction pressure to drop below 55 psig (3.8
bar) for more than a few seconds may overheat the
scrolls and cause early drive bearing damage. Never
install a system in the field and leave it unattended with
no charge, a holding charge, or with the service valves
closed without securely locking out the system. This
will prevent unauthorized personnel from accidentally
ruining the compressor by operating with no refrigerant
flow.
© 2020 Emerson Climate Technologies, Inc.
Refrigerant Retrofits
Only use approved refrigerants, lubricants, and
parts
in
accordance
compressor
specifications.
refrigerant from the system including the high and
low side. Use a tubing cutter to remove the
compressor.
These compressors are UL recognized and
use with any other refrigerant than originally
intended for use will void the compressor UL
recognition.
For a list of Emerson approved refrigerants
please refer to
Form 93-11, Refrigerants and
Lubricants Approved for Use in Copeland
Compressors.
13
AE4-1486 R1
with
the
system
and
Recover
all
the