4-3 Troubleshooting by symptoms

4-3-1 Communication error after finishing tracking (E202)

1. Check items
1) Is the communication cable short/open?
2) Is there a response from the indoor unit PCB?
2. Check procedure
Is there a response from the indoor unit PCB?
Is the power/communication
cable connected correctly?
Remove the communication cable
connecting the outdoor unit to indoor unit,
and measure the signal on LINE 2 of the
outdoor unit with a scope
In this case, is the
voltage waveform between the lines square
wave with amplitude over ±0.7V as shown
in the following picture?
Reconnect the cable connecting
the outdoor unit to the indoor unit
and restart the unit.
If the communication still doesn't work,
e r
l p
c a
t e
e h
outdoor unit PCB in order of mention.
+0.7V
-0.7V
cf.) If there is no oscillo scope, it can be replaced multimeter instead of osillo scope.
4-14
Samsung Electronics
Yes
Yes
Yes
indoor unit PCB and
Good
No
Check the communication cable and
replace the indoor unit PCB?
No
Connect the power/communication
cable correctly.
No
Check the communication
cable in each PCB
and replace the PCB
Bad
Troubleshooting
Samsung Electronics