Emerson Rosemount 625IR Manual page 44

Optical infrared gas detector
Table of Contents

Advertisement

Troubleshooting
January 2024
Recommended action
Contact support.
Source current loop error
Status type
Failure
Potential cause
The measured back current of the analog output is outside specification.
Recommended action
Contact support.
Sink current loop error
Status type
Failure
Potential cause
The measured back current of the analog output is outside specification.
Recommended action
Contact support.
Path transmission too high
Status type
Failure
Potential cause
Detector zeroing has been performed while the optics was dirty.
Recommended actions
S1 current error
Status type
Failure
Potential cause
Infrared (IR) source 1 issue.
Recommended action
Contact support.
S2 current error
Status type
Failure
44
1. Clean optics.
2. Zero the detector.
Manual
MS-00809-0100-3625
Emerson.com