hp ProLiant DL360 generation 3 server high-density deployment technical white paper
Table 2. ProLiant DL360 Generation 3 Server Parameters (continued)
Item
Maximum system measured input AC power
Maximum power supply rated input current
Maximum system measured input current
System Thermal Dissipation (per hour)
Relative Humidity (non-condensing)
Operating
Nonoperating
Note: The SA5302 option is a PCI card available from HP. Any third-party PCI cards used in the
ProLiant DL360 Generation 3 server must comply with the industry-standard PCI specifications
for dimension, weight, power, and thermal requirements.
input current and thermal dissipation calculations
The input power is the key in deriving the input current and thermal dissipation. For a given input
power, the input current will vary depending on the input voltage level.
The relationship among the current, the voltage and the power for the power supply input is as
follows:
Input Current = Input Power / Input Voltage
For example,
Input Current = 100 W /110 V = 0.91 A
Input Current = 100 W /208 V = 0.48 A
The input power of a server depends on the operational state of the system. For example, during
the initial power up, a server consumes more power due to the hard disk drive spin-ups. It should
be noted that in the ProLiant DL360 Generation 3 server, the two disk drives spin-up, one after
the other. Therefore, the peak input power requirement changes significantly when the first drive
is added, but not as much when the second drive is added. After the initial power up, the input
power varies depending on the operating system and the application software running on the
server. During standby, only the auxiliary portion of the power supply is consuming power to
support operations of a very limited part of the system, such as, the Remote Insight Lights-Out
Edition (RILOE) option, NICs, and so on.
@
100 V
240 V
100 V
240 V
100 V
240 V
100 V
240 V
5
Specification
361 W
343 W
4.5 A
1.8 A
3.7 A
1.5 A
1,232 BTUs
1,169 BTUs
10 to 90%
5 to 95%

Advertisement

Table of Contents