Introduction

KAIWEETS 208A Digital Clamp Meter is a TRUE-RMS 1000A AC Clamp Meter with integrated VFD Mode, Inrush Current capture.

Product Overview

Product Overview

  1. NCV Probe
  2. Current Sensing Jaw
  3. Flashlight
  4. Tactile Barrier
  5. Rotary Function Switch
  6. Function Buttons
  7. Display
  8. Alignment Marks
  9. Jaw Release
  10. INPUT Terminal (red test lead)
  11. COM Terminal (black test lead)
  12. Data Hold / Flashlight Switch

Symbol-Explanation

Symbol-Explanation

Function Buttons

Function Buttons - Part 1Function Buttons - Part 2

Advanced Functions

AC current measurement with "Inrush" function

Inrush current is the instantaneous high input current current drawn by a power supply or electrical equipment at turn-on. This arises due to the high initial currents required to charge the capacitors and inductors or transformers.
AC current

AC current measurement with Inrush function

  1. With the device to be tested turned off, tum the meter's dial to proper range (60/600Ã or 1000Ã).
  2. Center the jaw around the device's live wire.
  3. Push the "FUNC." button 2 times until the "INRUSH" symbol is displayed.
  4. Switch on the device. The inrush current (spike) is displayed in the meter's display.

Note: The measuring time of inrush current is about 100ms.

When an electrical device is first powered on, inrush current is the surge or momentary burst Of current that flows into it.

AC current measurement with "VFD" function (Variable Frequency Drive Filtering)

The VFD mode eliminates high frequency noise in voltage measurements by means of a low-pass filter. The VFD mode is designed for variable frequency drive (VFD) measurements. This mode is always active for AC measurements.

Turn the knob and select proper range (60/600Ã or 1000Ã), press the key until the "VFD" symbol is displayed.

Note: Please do not use VFD function to verify the presence of dangerous voltage or current, which may exceed the indicated value.

AC voltage measurement with "VFD" function

Turn the knob to or , press key until the "VFD" symbol is displayed.

Note: Please do not use VFD function to verify the presence of dangerous voltage or current, which may exceed the indicated value.

High-Impedance voltage measurement

High Impedance means high electrical Impedance. This is used to denote the input Impedance or output Impedance of electrical circuits and devices in particular. When measuring in the circuit, this has only a minor impact on the performance of the circuit, particularly in the case of sensitive electronic circuits or control circuits.

Low-Impedance voltage measurement

( )

mode allows you to measure AC/DC voltages with a low impedance in this mode, the Meter lowers the internal resistance to prevent 'phantom' voltage readings. As a result, the circuit is more heavily loaded than in the standard measuring mode.

warning Attention

  • When using (low input impedance) measurement, the continuous measurement time cannot exceed 1 minute.
  • Do not use LoZ mode to measure the voltage in the circuit that may be damaged due to the low impedance of this mode,

Operating Instructions

Insert and replace the batteries

Replace the batteries immediately when the symbol appears in the display. Disconnect the meter from the power source. Remove the test leads from the measuring device, loosen the screws on the back and remove the lower half of the housing, replace the old batteries and screw the cover back on.
Insert and replace the batteries

Turn on/off the meter

The device is switched on when the rotary switch (5) is set to a measuring function When the rotary switch is set to OFF, the measuring device is switched off.

Automatic shutdown

No operation in 15 minutes, the clamp meter beeps 3 times. Without further operation, the clamp meter beeps again and switches off automatically. Press any key to restore the clamp meter to operating status. The symbol appears on the display. To deactivate the automatic switch-off hold down the "FUNC," key for more than 2 seconds and switch on the clamp meter at the same time. The symbol disappears. Restart after switching off the meter, the automatic switch-off can be restored.

Auto-ranging

The meter automatically selects the measuring range that is best suited for the measurement performed. The measuring unit and resolution are adjusted at the same time.

AC zero input behavior of True-rms meters

Unlike averaging meters, which can accurately measure only pure sinewaves, True-rms meters accurately measure distorted waveforms. Calculating True-rms converters require a certain level of input voltage to make a measurement. This is why ac voltage and current ranges are specified from 5% of range to 100% of range. Non-zero digits that are displayed on a True-rms meter when the test leads are open or are shorted are normal. They do not affect the specified ac accuracy above 5% of range.

Connecting test leads

Do not test if leads are improperly seated. Results could cause intermittent display readings. To ensure proper connection, firmly press leads into the jack completely.
Connecting test leads

Making Measurements

AC current measurement

warning When making current measurements, disconnect the test leads from the Meter. Keep fingers behind Tactile Barrier(4).

When measuring current, center the conductor in the Jaw using the alignment marks on the Jaw.

  1. Turn the rotary switch to the correct current setting (60/600Ã, 1000Ã).
  2. Open the Jaw by pressing the Jaw Release and insert the conductor into the Jaw.
  3. Close the Jaw and center the conductor using the alignment marks.
  4. View the reading on the display.

AC current measurement

  • Suggest use the current clamp to surround one conductor.
  • If the supply and return conductors (e.g. L and N) are measured, the currents will cancel each Other out and no measurement will be displayed. The cables Of household appliances usually contain L and N conductors. A cable separator is required to measure with the current probe.
  • If several supply conductors are measured, the currents add up.

Frequency range: 0,1~600A: 40Hz~400Hz;
600~1000A: 40Hz~60Hz

AC/DC voltage measurement

warning Voltage above 750V (AC) / 1000V (DC) cannot be measured! When measuring high voltage, pay special attention to safety to avoid electric shock or injury.

AC/DC voltage measurement

  1. Set the rotary switch to or , press the "FUNC." key to switch between AC and DC voltage measurement.
  2. Plug the black test lead into the COM socket and the red test lead into the INPUT socket.
  3. Then bring the test probes into contact with the points to be measured.
  4. Read the measurement results on the display.

warning Attention

  • When using (low input impedance) measurement, the continuous measurement time cannot exceed 1 minute.
  • Do not use LoZ mode to measure the voltage in the circuit that may be damaged due to the low impedance of this mode.

High impedance voltage measurement: 10 MΩ
Low impedance voltage measurement: 300 kΩ

Frequency or duty cycle measurements (Hz%)

Frequency or duty cycle measurements (Hz%)

  1. Turn the rotary function switch to Hz%.
  2. Plug the black test lead into the COM socket and the red test lead into the INPUT socket.
  3. Connect the probes to the measuring points (connect to the measured power supply or to the parallel connection).
  4. Read the result on the display.
  • In Hz% mode, Range: 0~10MHz, Voltage sensitivity: 0.5~10V AC (as the frequency increases, the voltage should increase accordingly).
  • In V mode, Range: 10Hz~10kHz, Voltage sensitivity: >0.5V AC (as the frequency increases, the voltage should increase accordingly).
  • In A mode, Range: 10Hz~1kHz, Current sensitivity: >20A (as the frequency increases, the current should increase accordingly).

Resistance measurement Ω

Resistance measurement - Step 1
Resistance measurement - Step 2

  1. Turn the rotary function switch to for resistance measurement. It displays "MΩ" on screen.
  2. Turn off the circuit under test.
  3. Plug the black test lead into the COM socket and the red test lead into the INPUT socket.
  4. Then place the test probes in contact with the points at which the resistance must be measured.
  5. Read the result on the display.

Note: When measuring resistance on a circuit, the measured value can be influenced by other circuits.

Overload protection: 250V

Continuity test

Continuity test

  1. Turn the rotary switch to and press the "FUNC." key until appears on the display. The continuity test is now active.
  2. Plug the black test lead into the COM socket and the red test lead into the INPUT socket.
  3. Connect the probes to the circuit or component under test.
  4. If the resistance is <30 Ω, the LED indicator light is on at the same time, the resistance value will be displayed.

Note: When measuring resistance on a circuit, the measured value can be influenced by other circuits.

Test Voltage Approx. 1V
Overload protection: 250V

Diode test

  1. Turn the rotary function switch to , press the press the "FUNC." key 2 times until appears on the display.
  2. Remove power from the circuit being tested.
  3. Connect the black test lead to the COM terminal and the red test lead to the INPUT terminal.
  4. Connect the black test lead to the cathode side and the red test lead to the anode side of the diode being tested.
  5. Read forward bias voltage value on the LCD.
  6. If the polarity of the test leads is the reverse of the diode polarity, the LCD reading shows "OL". This can be used for distinguishing the anode side and cathode side of a diode.


To avoid electrical shock when testing diodes in a circuit, make sure the power to the circuit is turned off and all capacitors are discharged.

Overload protection: 250V

Capacitance measurement

  1. Remove power from the circuit being tested. Turn the rotary function switch to , press the "FUNC." key 3 times until "nf" appears on the display.
  2. Connect the black test lead to the COM terminal and the red test lead to the INPUT terminal.
  3. Connect the probes across the circuit or (capacitance) component to be tested.
  4. View the reading on the display,


To avoid electrical shock When testing capacitance in a circuit, make sure the power to the circuit is turned off and all capacitors are discharged.
When measuring small capacitors, turn on the relative value (REL) to subtract the residual capacitance value of the meter and the conductor when the test probe is open.
When measuring a capacitance greater than 100uF, it will take a long time to measure correctly.

Overload protection: 250V

Temperature measurement

  1. Turn the rotary function switch to ºC / ºF position.
  2. Insert the K-type thermocouple into the meter, the positive pole (red) of the thermocouple into the INPUT input and the negative pole (black) into the COM input.
  3. Contact the thermocouple probe with the measurement object, then the reading appears on the display.


To avoid possible electric shock DO NOT apply the probe tip to any conductor that is greater than 30 V ac, 42 V peak or 60 V dc to earth.

Note: It takes a long time for the cold end of thermocouple to be restored in the instrument to achieve thermal balance with the environment.

Non-contact AC voltage detection (NCV)

warning When using NCV function, please remove the probe, otherwise the detection sensitivity will be affected.

  1. Turn the knob to NCV/LIVE, the "" symbol is displayed.
  2. Then the NCV probe will be approached the detected point gradually.
  3. When the signal of weak electromagnetic field is sensed, the character "- - L" is displayed, the buzzer emits a slow beep sound and the green LED indicator light is on.
  4. When the signal of strong electromagnetic field is sensed, the character "- - H" is displayed, the buzzer emits a quick beep sound and the red LED indicator light is on.

Live detection

warning Remove black test lead otherwise the detection sensitivity will be affected.

  1. Turn the knob to NCV/LIVE, press key until the "" Symbol is displayed.
  2. Insert the red test lead to INPUT terminal.
  3. Connect the red test lead to the conductor to be for measurement.
  4. When the signal of weak electromagnetic field is sensed, the character "- - L" is displayed, the buzzer emits a slow beep sound and the green LED indicator light is on.
  5. When the signal of strong electromagnetic field is sensed, the character "- - H" is displayed, the buzzer emits a quick beep sound and the red LED indicator light is on. In general. it means the tested wire is live wire.

Specification

Display: 6000 counters, True RMS

Display update frequency: approx. 3 Hz

Measuring impedance: 10 MΩ (V range)

Operating voltage: 3 x AAA (1.5V)

Weight: approx. 700g

Dimension: 285mm x 135mm x 60mm

Security standard: IEC 61010-1
IEC 61010-2-032: CAT Ill 1000V / CAT IV 600V
IEC 61010-2-033: CAT Ill 1000V / CAT IV 600V

Pollution level: 2

Operating temperature: 0 to +40 ºC

Operating humidity: <80%

Operating height: 0 to max. 2000 m

Storage temperature: -10 to +60 ºC

Air humidity in storage: <70%

Accuracy

Accuracy - Part 1Accuracy - Part 2

Maintenance

  • To avoid electrical shock, disconnect test leads from the Meter before removing its back cover. Never use the Meter with the back cover removed.
  • Repairs or servicing not covered in this manual should be performed only by qualified personnel.

  • To avoid contamination or static damage, do not touch the circuit board without proper static protection.
  • If the Meter is not going to be used for a long time, remove the battery. Do not store the Meter in a high temperature or a high humidity environment.

Cleaning the Meter

  • To avoid damaging the meter, do not use abrasives or solvents on this instrument.
  • Periodically clean the Meter by Wiping it With a damp cloth and mild detergent.
  • Do not get water inside the case. This may lead to electrical shock or damage to the instrument.
  • Wipe the contacts in the socket with a clean cotton swab soaked in alcohol.

Safety information


Read First

To avoid possible electric shock or personal injury, please obey the following instructions:

  • Use the Meter only as specified in this manual or the protection provided by the Meter might be impaired.
  • Avoid working alone so assistance can be rendered.
  • Never measure AC current while the test leads are inserted into the input jacks.
  • Do not use the Meter in wet or dirty environments.
  • Inspect the test leads before use. Do not use them if insulation is damaged or metal is exposed.
  • Check the test leads for continuity. Replace damaged test leads before using.
  • Use extreme caution when working around bare conductors or bus bars. Contact with the conductor could result in electric shock.
  • Do not hold the Meter anywhere beyond the tactile barrier.
  • Do not apply more than the rated voltage, as marked on the Meter, between the terminals or between any terminal and earth ground,
  • Remove test leads from the Meter before opening the Meter case.
  • Never operate the Meter with the back cover removed or the case open.
  • Never remove the back cover or open the case of an instrument Without first removing the test leads or the jaws from a live conductor.
  • Use caution when working with voltages above 30 V ac RMS, 42 V ac peak, or 60 V dc. These voltages pose a shock hazard.
  • Do not attempt to measure any voltage that might exceed the maximum range of the Meter - 1000 V RMS.
  • Do not operate the Meter around explosive gas, vapor, or dust.
  • When using probes, keep fingers behind the finger guards,
  • When making electrical connections, connect the common test lead before connecting the live test lead; when disconnecting, disconnect the live test lead before disconnecting the common test lead.
  • Disconnect circuit power and discharge all high-voltage capacitors before testing resistance, continuity, or diodes.
  • Check the operation of the meter at a known source before and after use.

Contact us on Facebook: @kaiweetstools

Contact us: support@Kaiweets.com

Documents / Resources

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download KAIWEETS HT208A - Digital Clamp Meter with Inrush Manual

Advertisement

Need Assistance?

Do you have a question about the HT208A that isn't answered in the manual? Leave your question here.

Error while submitting your question. Please, reload page and try again.

Thank you! Your question has been received!

Table of Contents