Technical Data; Declaration Of Conformity; Electrical Data - Swegon REACT V BMBa Instructions For Use Manual

Table of Contents

Advertisement

REACT V BMB

Technical data

IP class:
Corrosivity class:
Pressure class:
Leakage classes according to SS-EN 1751
- Leakage class, casing:
- Leakage class circular damper, closed:
- Leakage class rectangular damper,
closed:
Running times open/close (90°):
5 Nm:
10 / 20 Nm:
Ambient temperature
Operation:
Storage:
RH:
CE marking:

Electrical data

Power supply:
Fixed connection cable,
1000 mm with cable size.
Power consumption, for transformer rating:
REACT V BMB 5 Nm
REACT V BMB 10 Nm
REACT V BMB 20 Nm
12
Swegon reserves the right to alter specifications.
IP54
100 s
150 s
0 – +50°C
-20°C – +80°C
5 – 95%
(non-condensing)
2006/42/EC (MD)
2014/30/EU (EMC)
2011/65/EU (RoHS2)
24 V AC/DC ±15% 50 - 60 Hz
6 x 0.75 mm
2.0 W
4.0 VA
3.0 W
5.0 VA
3.0 W
5.5 VA
20230929

Declaration of Conformity

Swegon AB hereby affirms that:
C3
REACT V BMB complies with the essential characteristic
A
demands and relevant regulations specified in the directives,
2006/42/EC (MD), 2014/30/EU (EMC) and 2011/65 EU
(RoHS2):
C
The following standards have been observed:
4
3
EN ISO 12100:2010
EN 60204-1:2006
EN 60730-1:2011
EN 61000-6-2:2007
EN 61000-6-3:2007
Person responsible for this declaration:
Name: Freddie Hansson, R&D Manager Tomelilla
Address: Industrigatan 5, 273 21 Tomelilla, Sweden
Date: 230427
2
This declaration is applicable only if the product has been
installed according to the instructions in this document
and if no modifications or changes have been made on
this product.
References
www.swegon.com
Building Materials Declaration
REACT V BMB Product data sheet
REACT Belimo – Description of functions & wiring diagram
REACT Belimo – Modbus settings
Safety of machinery - General principles for
design - Risk assessment and risk mitigation
Safety of machinery - Electrical equipment of
machines - Part 1: Generic standards
Automatic electrical controls for household and
similar use - Part 1 Generic standards
Electromagnetic compatibility (EMC). Generic
standards. Immunity for industrial environments
Electromagnetic compatibility (EMC). Generic
standards. Emission standard for residential,
commercial and light-industrial environments