General; Home; Indoor Temperature Limits - Honeywell TC300 Integration Manual

Bacnet integration guide
Hide thumbs Also See for TC300:
Table of Contents

Advertisement

General

Name
Cfg_Thermostat_TstUnitSel
Cfg_BrandType

Home

Name
Cfg_StdbyConfig
Cfg_Thermostat_ClAdjStPt
Cfg_Thermostat_HtAdjStPt

Indoor temperature limits

Name
Cfg_SpcAlarm_TempHighLim
Cfg_SpcAlarm_TempLowLim
Cfg_DaTAlarm_TempHighLim
Cfg_DATAlarmTempLowLim
Cfg_PipeTempHeatThreshold
58
Table 22 General
BACnet
BACnet
Object
Object
Type
Instance
Binary
136
Value
Multistat
505
e Value
Table 23 Home
BACnet
BACnet
Object
Object
Type
Instance
Binary
2034
Value
Analog
256
Value
Analog
257
Value
Table 24 Indoor temp limits
BACnet
BACnet
Object
Object
Type
Instance
Analog
254
Value
Analog
255
Value
Analog
332
Value
Analog
333
Value
Analog
2070
Value
Default
Range
Value
0
Fahrenheit=0,
Celsius=1
1
enum{Honeywell=1
Alerton=2,
None=3}
Default
Range
Value
0
StandbyAsUnoccupied
=0,
StandbyAsOccupied=1
-45 to 45 °F
-45 to 45 °F
Default
Range
Value
90 °F
90 to 150 °F
45 °F
0 to 60 °F
140 °F
70 to 180 °F
45 °F
35 to 65 °F
80 °F
70 to 90 °F
Description
Thermostat unit definition
(Imperial/ Metric)
Vendor ID and Vendor
name will be changed
when modify brand type.
Description
Standby action
Temporary cool
setpoint adjustment
from User or from the
supervisor.
Temporary heat
setpoint adjustment
from user or from the
supervisor.
Description
Space temperature alarm
high limit
Space temperature alarm
low limit
Discharge air temperature
alarm high limit
Discharge air temperature
alarm low limit
Pipe sensor threshold for
heating