Honeywell TC300 Integration Manual page 34

Bacnet integration guide
Hide thumbs Also See for TC300:
Table of Contents

Advertisement

Name
Cfg_ModHeatMin_Output
Cfg_ModHeatAction
Cfg_ModCoolMin_Output
Cfg_ModCoolAction
Cfg_VarSpeedFanType
Cfg_ModHeatMax_Output
Cfg_ModCoolMax_Output
Cfg_PipeSensChar
Cfg_DASensChar1
Cfg_LeakDetectorSensorChar
34
Table 7 IO configuration (Continued)
BACnet
BACnet
Object
Object
Type
Instance
Analog
1475
Value
Binary
380
Value
Analog
1476
Value
Binary
381
Value
Multistate
373
Value
Analog
1477
Value
Analog
1478
Value
Multistate
2005
Value
Multistate
503
Value
Binary
455
Value
Default
Range
Value
2 V
0 to 9 V
0
Direct=0,
Reverse=1
2 V
0 to 9 V
0
Direct=0,
Reverse=1
2
enum{0-10V=1,
2-10V=2}
10 V
1 to 10 V
10 V
1 to 10 V
3
enum{
NTC10KTypeII=1,
NTC10KTypeIII=2,
NTC20K=3}
3
enum{
NTC10KTypeII=1,
NTC10KTypeIII=2,
NTC20K=3}
1
NormallyOpen=0,
NormallyClosed=1
Description
Minimum output
voltage when
modulating heating
is enabled
Modulating heat
polarity selection
Minimum output
voltage when
modulating cooling
is enabled
Modulating cool
polarity selection
Variable fan speed
type characteristic
selection
Maximum voltage on
heating output.
Maximum voltage on
cooling output.
Pipe sensor type
Discharge air sensor
type
Leak detector/Drain
pan sensor
characteristics
IO configuration