40
D1M 20 POWER METER USER MANUAL
DELAY
DELAY is used to verify whether the variable value really exceeds the limit or is recovered, and its setting
range is 0~900s.
CONF>ALAM>DELAY
LOG
All alarms are set by default in log mode, which means that alarms are stored in flash memory when the
alarm is triggered.
CONF>ALAM>LOG
PORT
Each alarm event can be connected with certain DO, and different alarms can be connected to the same
DO.
CONF>ALAM>PORT
• The optional DOs include DO1, DO2 and NONE.
Only the DOs configured as alarm output can appear in the list. For details, see
"7.3.Input/output
(I/O)".