Step Component
5
Termina
WARNING
attachmentl
plate
Do not detach the inverter for 5 minutes after
turning off the breaker as doing so may cause
electric shocks.
1. Detachment
1) Remove the front panel and upper panel. [Step
1]
2) Remove the 4 screws fixing the terminal
attachment plate to remove it. (M4×8, 4) (Fig.
5-1, 5-2)
3) Cut the banding band. (1 position) (Fig. 5-3)
4) Remove the screws from the terminal
attachment plate and the terminal. (M4×16, 2)
(Fig. 5-3)
5) Lift the terminal attachment plate up and
remove the tab. (Fig. 5-4)
2. Attachment
1) Install it in the reverse of the procedure to
remove it.
CAUTION
To remove the round terminal and install it
again, face the flat surface up and tighten
the terminal with a tightening torque of
2.5±0.1N ・ m.(Fig. 5-5,5-6 )
Procedure
149
Remarks
Terminal
attachment plate
Screws (3 positions)
(Fig. 5-1)
Banding band
(1 position)
Screws (2 positions)
(Fig. 5-3)
Round terminal (2 positions)
(Fig. 5-5)
Screws (1 position)
(Fig. 5-2)
tab
(1 position)
(Fig. 5-4)
Flat surface
(Fig. 5-6)