X93;E3” Abnormal High Pressure (Detected By The Hps) - Daikin EHYHBH05AAV3 Service Manual

Table of Contents

Advertisement

Error Codes: Outdoor Units

“E3” Abnormal High Pressure (Detected by the HPS)

4.2
1
Remote controller
display
Method of
malfunction
detection
Malfunction
decision conditions
3
Supposed causes
4
5
HPS settings
Part 4 – Troubleshooting
E3
The protection device circuit checks continuity in the high pressure switch.
When the high pressure switch is actuated
Actuating pressure:
Faulty high pressure switch
Disconnection in high pressure switch harness
Faulty connection of high pressure switch connector
Clogged hydro-box suction filter (in heating operation)
Dirty outdoor unit heat exchanger
Faulty outdoor unit fan
Refrigerant overcharge
Stop valve is left in closed
The table below contains the preset HPS values.
Open
4.0 MPa +0/-0.15
High pressure switch
Close
3.0 +/-0.15
104
ESIE13-02A
Fuse
6.3A/250V