1. Introduction GPS4827 OmniOn Power developed the Galaxy Power System GPS 4827 to support -48 volt telecommunications powering solutions in worldwide markets. The GPS 4827 combines 50-ampere, fan-cooled, switchmode rectifiers, microprocessor control technologies, battery and load disconnect/reconnect options, and a comprehensive line of fuse and circuit breaker dc distribution options in a modular front-access design.
Overview Modular external return bus bar kits are available for the GPS4827 system. These kits are alternatives to the standard internal return buses. These kits allow for modular growth of the bars from bay to bay and offer additional cable landings.
Page 48
A battery potential input is required, which must use an external 1K ohm, 2W current limiting resistor at the source if not using standard OmniOn Power LVD circuit boards or controller. This circuit is used to inform Galaxy that the monitoring circuit of a Low Voltage Disconnect device has failed.
Page 52
A ground referenced RS-232 local port is provided at the front of the display to allow easy connection to a personal computer or terminal using ANSI T1.317 object oriented command language. OmniOn Power’s EasyView is also available to provide a user friendly system interface locally or remotely. See figure 4-6.
Need help?
Do you have a question about the GPS4827 and is the answer not in the manual?
Questions and answers