11. Wiring (For details, refer to the installation manual of each indoor/outdoor unit and controller.)
11.1. Caution
1 Follow ordinance of your governmental organization for technical standard
related to electrical equipment, wiring regulations and guidance of each
electric power company.
2 Wiring for control (hereinafter referred to as transmission line) shall be
(5 cm or more [2 in or more]) apart from power source wiring so that it is
not influenced by electric noise from power source wiring. (Do not insert
transmission line and power source wire in the same conduit.)
3 Be sure to provide designated grounding work to the outdoor unit.
4 Give some allowance to wiring for the electrical part box on the indoor and
outdoor units, because these boxes are sometimes removed at the time of
service work.
5 Never connect the main power source to terminal block of transmission line.
If connected, electrical parts will burn out.
6 Use 2-core shield cable for the transmission line. If transmission lines of
different systems are wired with the same multiplecore cable, the resultant
poor transmitting and receiving will cause erroneous operations.
7 Only the transmission line specified should be connected to the terminal
block for outdoor unit transmission.
Erroneous connection does not allow the system to operate.
8 When connecting a System Controller to outdoor units or performing a
group operation of indoor units that are connected to different outdoor
units, a transmission line for centralized control is required. When using a
transmission line for centralized control, connect the transmission line (non-
polar 2 core wire) to all TB7 terminals between all outdoor units.
9 Grouping is set by operating the remote controller.
11.2. Control box and connecting position
of wiring
1 Outdoor unit
1. Remove the front panel of the control box by removing the 4 screws and
pushing it up a little before pulling it out.
2. Connect the indoor - outdoor transmission line to the terminal block (TB3) for
the indoor - outdoor transmission line.
If multiple outdoor units are connected in the same refrigerant system,
daisy-chain TB3 (M1, M2, ground terminal
the indoor - outdoor transmission line for the outdoor units to TB3 (M1, M2,
ground terminal
) of only one of the outdoor units.
3. Connect the transmission lines for centralized control (between the centralized
control system and the outdoor unit of different refrigerant systems) to the
terminal block for centralized control (TB7). If the multiple outdoor units are
connected to the same refrigerant system, daisy-chain TB7 (M1, M2, terminal
S) on the outdoor units in the same refrigerant system. (*1)
*1 : If TB7 on the outdoor unit in the same refrigerant system is not daisy-
chained, connect the transmission line for centralized control to TB7
on the OC (*2). If the OC is out of order, or if the centralized control is
being conducted during the power supply shut-off, daisy-chain TB7 on
the OC and OS. (In the case that the outdoor unit whose power supply
connector CN41 on the control board has been replaced with CN40
is out of order or the power is shut-off, centralized control will not be
conducted even when TB7 is daisy-chained.)
*2 OC and OS of the outdoor units in the same refrigerant system are
automatically identified. They are identified as OC and OS in descending
order of capacity. (If the capacity is the same, they will be in ascending order
of their address number.)
4. In the case of indoor-outdoor transmission line, connect the shield ground
to the ground terminal
. In the case of transmission lines for centralized
control, connect it to the shield terminal (S) on the terminal block for
centralized control (TB7). Furthermore, in the case of the outdoor units
whose power supply connector CN41 is replaced with CN40, short circuit the
shield terminal (S) and the ground terminal
5. Fix the connected wires securely in place with the cable strap at the bottom
of the terminal block. External force applied to the terminal block may
damage it and may cause a short circuit, ground fault, or a fire.
[Fig. 11.2.1]
A
Power supply terminal block
Terminal block for indoor –
(TB1)
outdoor transmission line
Control box
L1 L2 L3
C
A Power source
C Ground screw
) on the outdoor units. Connect
in addition to the above.
B
Terminal block for
centralized control
(TB3)
(TB7)
B Transmission line
[Fig. 11.2.2]
A
C
B
A Cable strap
C Transmission line
When using wire size AWG 6, be sure to use knockout hole 4.
When using wire size AWG 4, AWG 3, AWG 2, or AWG 1, be sure to use
knockout hole 2.
When using wire size AWG 0, AWG
hole 5.
If there are any gaps around the wires, please be sure to fill these in with a
suitable material.
2 Conduit tube installation
Close by hammering the knockout holes for the conduit tube located on the
base and the bottom part of the front panel.
When installing the conduit tube directly through the knockout holes, remove
the burr and protect the tube with masking tape.
Use the conduit tube to narrow down the opening if there is a possibility of
small animal's entering the unit.

11.3. Wiring transmission cables

1 Types of control cables
1. Wiring transmission cables
Types of transmission cables: Shielding wire CVVS, CPEVS or MVVS
Cable diameter: More than 1.25 mm
Maximum wiring length: Within 200 m [656 ft]
Maximum length of transmission lines for centralized control and indoor/
outdoor transmission lines (Maximum length via outdoor units): 500 m
[1640 ft] MAX
The maximum length of the wiring between power supply unit for
transmission lines (on the transmission lines for centralized control) and
each outdoor unit and system controller is 200 m [656 ft].
2. Remote control cables
M-NET Remote Controller
Kind of remote control cable
Sheathed 2-core cable (unshielded) CVV
0.3 to 1.25 mm
Cable diameter
1.25 mm
When 10 m [32 ft] is exceeded, use cable
Remarks
with the same specifications as 1. Wiring
transmission cables.
MA Remote Controller
Kind of remote control cable
Sheathed 2-core cable (unshielded) CVV
0.3 to 1.25 mm
Cable diameter
1.25 mm
Remarks
Within 200 m [656 ft]
* Connected with simple remote controller.
2
1
3
4 5
B Power source line
0
/
, or AWG
0
/
, be sure to use knockout
2
3
[AWG 16]
2
[AWG 22 to 16] (0.75 to
2
[AWG 18 to 16])*
2
[AWG 22 to 16] (0.75 to
2
[AWG 18 to 16] )*
2
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

City multi puhy-hp-tjmu-a-bs

Table of Contents