PSR-PS40
SIL coupling relay
Data sheet
106254_en_03
1

Description

Intended Use
The SIL coupling relay is used to adjust the power and for electrical
isolation in high- and low-demand applications. The coupling relay
safely interrupts circuits. The device performs a self test the
moment it is switched on and prevents the enable contacts from
being closed in the event of an error. The category 3 device is
designed for installation in zone 2 potentially explosive areas.
Possible signal generators
Failsafe controllers
Contact type
1 undelayed enabling current path
1 digital signal output
1 Start circuit
The enabling current path drops out without delay according
to stop category 0 (EN 60204-1).
Control
Single-Channel
Automatic start
WARNING: Risk of electric shock
Observe the safety regulations and installation notes in the corresponding section.
Make sure you always use the latest documentation.
It can be downloaded from the product at phoenixcontact.net/products.
This document is valid for the products listed in the "Ordering data".
This document meets the same requirements as the original operating instructions with respect to the
contents.
DOWNLOADED FROM WWW.SCATTS.CO.UK
© PHOENIX CONTACT
2018-10-19
Achievable safety integrity
Suitable for high and low-demand applications up to
SIL 3 according to IEC 61508, IEC 61511, and
IEC 50156
Additional features
Easy proof test:
   - Self-monitoring, with device-internal locking
   - Visually on the device
Additional diagnostics and status information
   - Error indication via M1
Readback of field devices possible
Integrated test pulse filter.
Corrosion protection through lacquering the printed-
circuit board
Fixed screw connection
6.8 mm housing width
Approvals
  
DOWNLOADED FROM WWW.SCATTS.CO.UK

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PSR-PS40 and is the answer not in the manual?

Questions and answers

Summary of Contents for Phoenix Contact PSR-PS40

  • Page 1: Description

    DOWNLOADED FROM WWW.SCATTS.CO.UK PSR-PS40 SIL coupling relay Data sheet 106254_en_03 © PHOENIX CONTACT 2018-10-19 Description Intended Use Achievable safety integrity The SIL coupling relay is used to adjust the power and for electrical – Suitable for high and low-demand applications up to isolation in high- and low-demand applications.
  • Page 2: Table Of Contents

    Operating and indication elements ..................15 Mounting and removing ......................16 Wiring ............................ 16 Startup........................... 17 Calculating the power dissipation ..................17 Proof test ..........................18 Diagnostics..........................18 Application examples ......................19 Attachment ..........................21 106254_en_03 PHOENIX CONTACT 2 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 3: Ordering Data

    250 V AC/DC (Observe the load curve) Limiting continuous current 6 A (High demand) 4 A (Low demand) Inrush current min. 3 mA max. 6 A Sq. Total current 36 A (observe derating) + ... + I 106254_en_03 PHOENIX CONTACT 3 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 4 Safe isolation, reinforced insulation 6 kV from control circuit, See “Insulation coordination” start circuit, signal output to the enabling current path; 4 kV / basic insulation between all current paths and housing Degree of pollution 106254_en_03 PHOENIX CONTACT 4 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 5 Class I, Div. 2, Groups A, B, C, D, T4 Shipbuilding ( 11253-14 HH ) C, EMC2 Environmental simulation test ISA-S71.04 (G3) Functional Safety in accordance with IEC 61508 to SIL 3 Safety data Stop category according to IEC 60204 106254_en_03 PHOENIX CONTACT 5 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 6 99.72 % SD 0 FIT SU 1891 FIT DD 0 FIT DU 5.236 FIT Total 1896 FIT MTBF 52 Years 2.29 x 10 (For T1 = 1 year) Safety parameters for  EN 50156 106254_en_03 PHOENIX CONTACT 6 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 7: Notes Regarding Documentation

    Knowledge of the following topics is required: – Qualified personnel who install and operate safety – Handling safety components equipment in machines and systems. – Valid EMC regulations – Valid regulations governing occupational safety and accident prevention 106254_en_03 PHOENIX CONTACT 7 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 8: Safety Regulations And Installation Notes

    • Before working on the device, disconnect the power. • Carry out wiring according to the application. Refer to the “Application examples” section for this. 106254_en_03 PHOENIX CONTACT 8 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 9 106254_en_03 PHOENIX CONTACT 9 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 10: Specific Terms And Conditions Of Use For Atex/Iecex

    Rating plate (laser printing) Installation in areas with a danger of dust explosions WARNING: Explosion hazard The device is not designed for use in atmospheres with a danger of dust explosions. 106254_en_03 PHOENIX CONTACT 10 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 11: Function Description

    “Proof test” and “Diagnostics”. Test pulse filter By filtering the control controller test pulses, premature failure of the forcibly guided safety relay is prevented. 106254_en_03 PHOENIX CONTACT 11 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 12: Basic Circuit Diagram

    This means that SELV circuits of U  25 V AC or U  60 V DC and circuits with higher voltages can be mixed. 106254_en_03 PHOENIX CONTACT 12 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 13: Derating

    Derating curve - vertical mounting position, without spacing Expanded ambient temperature range (with no distance): up to +70 °C Conditions: Max. rated control circuit supply voltage 24 V DC Max. total current of the enabling current path 1 A 106254_en_03 PHOENIX CONTACT 13 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 14: Load Curve

    Expanded ambient temperature range (with no distance): up to +70 °C Conditions: Max. rated control circuit supply voltage 24 V DC Max. total current of the enabling current path 250 mA 106254_en_03 PHOENIX CONTACT 14 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 15: Operating And Indication Elements

    K1/2 Status indicator safety circuit; LED (green) Error LED (red) Diagnostics LED (green)         PS 40         13/14 Enabling current path, undelayed Signal output (PNP) 106254_en_03 PHOENIX CONTACT 15 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 16: Mounting And Removing

    Horizontal mounting position Mounting position with device front facing upwards Note the derating curves for various mounting positions. See section "Derating". Figure 12 Signal generator connection versions Single-channel control via failsafe controller 106254_en_03 PHOENIX CONTACT 16 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 17: Startup

    Signal output M1 is not active. Power dissipation in mW Applied operating voltage Rated control circuit supply voltage Rated control supply current Number of enabling current paths used Contact load current 106254_en_03 PHOENIX CONTACT 17 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 18: Proof Test

    24 V A1 is activated. The Y1/Y2 start circuit Proof test not passed. is closed. *) The signaling output M1 is not safety-relevant and therefore not suitable for the proof test. 106254_en_03 PHOENIX CONTACT 18 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 19: Application Examples

    PLC, safety relay, and external contactors K1 and K2 are located in the same electrical installation space. 24 V DC SIS / FS-PLC Logic PSR-PS40 Figure 14 High-demand application with failsafe controller 106254_en_03 PHOENIX CONTACT 19 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 20 2.29 x 10 (for T1 = 1 year) external contactors K1 and K2 are located in the same electrical installation space. 24 V DC SIS / FS-PLC Logic PSR-PS40 Figure 15 Low-demand application with failsafe controller 106254_en_03 PHOENIX CONTACT 20 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 21: Attachment

    If derating is specified, offset all the points of the derating curve by the corresponding factor in accordance with the table below. 106254_en_03 PHOENIX CONTACT 21 / 22 DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 22 Info box for application example 1 deleted 2015-07-14 Texts / safety notes regarding ATEX deleted 2018-10-19 New edition of the data sheet; ATEX/IECEx approval data added PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany 106254_en_03 22 / 22 phoenixcontact.com DOWNLOADED FROM WWW.SCATTS.CO.UK...
  • Page 23 At Scattergood & Johnson Ltd, we pride ourselves on being a technical distributor to specialist industries. Working with a range of quality product suppliers across a number of specialist markets, we are not your average ‘box shifter’ - we are your technical and supply chain partner. We fully support every product we sell - for free! Our internal team and external sales engineers can answer any product or application question, no matter the complexity.