SFC 125 / SFB 125   -  Fuel Conversion to 
Natural Gas - P-807
 
Note
If converting from   n atural gas to propane, order the propane conversion parts kit (IBC Part # P-806) 
from your authorized IBC distributor.
Use the natural gas conversion parts kit if the fuel source at the site uses natural gas and the appliance has 
been set up (factory fire-tested) to operate with Propane. Check the rating plate on the appliance to see which 
fuel source the particular appliance has been set up with.
Using this conversion kit, a qualified technician will need to:
 1.  Perform a fuel conversion.
 2.  Perform a combustion test.
 3.  Fill in the information required on the fuel conversion labels, and affix them to the appliance after the 
conversion is completed.
Warning
This conversion kit shall be installed by a qualified service agency in accordance with the 
manufacturer's instructions and all applicable codes and requirements of the authority having 
jurisdiction. If the information in these instructions is not followed exactly, a fire, an explosion or 
production of carbon monoxide may result causing property damage, personal injury or loss of life. 
The qualified service agency is responsible for the proper installation of this kit. The installation is not 
proper and complete until the operation of the converted appliance is checked as specified in the 
manufacturer's instructions supplied with the kit.
The appliance will automatically de-rate the maximum input at a rate of approximately 2% per 1,000' above 
4,500'. The gas valve's zero-governor will ensure that the gas-air mixture is not affected at altitude.
Included with the conversion kit:
 
Part #
LP orifice # 450 
180-228
150-175 
Orifice   O -ring 19 x 2                          
080-304
Rating plate overlay 
080-107 
Gas valve conversion label 
080-245
Installer Identification label    
120-245E2
 
Description
 
Quantity
1
1
1
1
1
| 1

Advertisement

loading

Summary of Contents for IBC P-807

  • Page 1 SFC 125 / SFB 125   -  Fuel Conversion to  Natural Gas - P-807   Note If converting from   n atural gas to propane, order the propane conversion parts kit (IBC Part # P-806)  from your authorized IBC distributor. Use the natural gas conversion parts kit if the fuel source at the site uses natural gas and the appliance has  been set up (factory fire-tested) to operate with Propane. Check the rating plate on the appliance to see which  fuel source the particular appliance has been set up with. Using this conversion kit, a qualified technician will need to:  1.  Perform a fuel conversion.  2.  Perform a combustion test.  3.  Fill in the information required on the fuel conversion labels, and affix them to the appliance after the  conversion is completed. Warning This conversion kit shall be installed by a qualified service agency in accordance with the  manufacturer’s instructions and all applicable codes and requirements of the authority having  jurisdiction. If the information in these instructions is not followed exactly, a fire, an explosion or  production of carbon monoxide may result causing property damage, personal injury or loss of life.  The qualified service agency is responsible for the proper installation of this kit. The installation is not  proper and complete until the operation of the converted appliance is checked as specified in the  manufacturer’s instructions supplied with the kit. The appliance will automatically de-rate the maximum input at a rate of approximately 2% per 1,000’ above  4,500’. The gas valve's zero-governor will ensure that the gas-air mixture is not affected at altitude. Included with the conversion kit:       Part # Description Quantity LP orifice # 450  180-228 150-175 ...
  • Page 2 Combustion Test Target Ranges Figure 1 Gas valve and fan The Low Fire (zero-offset) valve adjustment cap on the gas valve has been factory set. Do not adjust this screw in  the field unless indicated   i n these instructions.  After converting the appliance to natural gas, a combustion (CO ) reading must be taken by a qualified technician  using properly functioning and calibrated combustion analyzing equipment and the results compared to the values  in Table 1.  Value (%) at Low Fire with front   Value (%) at High Fire with front  Natural Gas cover open cover open Max. CO  value 10.1% Actual Value at High Fire  Min. CO  value 9.1% 9.1% Table 1 values at high and low fire...
  • Page 3: Fuel Conversion Instructions

    Alternative Naturel Gas Orifice - calorific values between 750-900 BTU/FT To perform a fuel conversion:  1.  Turn off the gas supply at the manual gas valve.  2.  Disconnect the electrical power.  3.  Disconnect the nut at the gas valve outlet (top of the gas valve), and remove the O-ring and orifice.  4.  Insert the correct orifice into the O-ring, and re-install into the nut at the gas valve outlet (top of the gas  valve), and then tighten the nut.  5.  Restore the gas supply by opening the gas control valve.  6.  Test for leaks by using an approved leak detection solution on all joints.  7.  Power on the appliance. Now, carefully follow the procedures on Combustion Testing and Adjustment. SFC 125 / SFB 125 - Fuel Conversion to Natural Gas - P-807...
  • Page 4 Combustion Testing and Adjustment Danger A combustion test checks that the gas valve is operating properly in the field. To perform a combustion  test, you must be a qualified, trained and licensed gas fitter. Making adjustments to the gas valve without a properly calibrated gas combustion analyzer and by  people who are not trained and experienced in its use is forbidden. Failure to use an analyzer can  result in an immediate hazard. Model Number High Fire Input  /  125 MBH SFC 16-125 SFB 16-125 Table 4 Rated input of a converted appliance Normal ignition system sequence of operation: The appliance's control, upon a call for heat or DHW, turns on the combustion fan for a 5-second pre-purge, then  energizes the spark electrode and gas valve for a 5-second trial for ignition. If the burner does not light, the process is repeated until the burner lights and flame is detected. After 4  unsuccessful trials for ignition, the appliance locks out and will need to be manually reset by pressing the Return  Arrow   button.  To perform a combustion test and adjustment:  1.  Turn off the appliance’s manual gas valve.   2.  With a Torx 15 screwdriver, open the inlet gas supply pressure test port by  turning its screw 1 full turn counterclockwise.  3.  Attach a manometer to the inlet pressure test port and turn on gas to  appliance. Static manometer reading should be ideally   1 1" w.c. for Propane. Minimum and maximum static pressure must be between 5" and 14" ...
  • Page 5  b.  Make tiny adjustments, typically less than 1/8th of a turn at a time. Turn the screw clockwise to  increase CO  and counter-clockwise to reduce CO . If the target cannot be met, even after a half  turn, contact the factory.   c.  When finished, replace the Low Fire cap, and leave the manual mode by pressing + AND -  simultaneously.  7.  Switch off the appliance by pressing the space above the dot.   8.  Turn off the gas at the appliance's manual gas valve.  9.  Remove the flue gas analyzer from the test port, and reinstall the test port cap.   10.  Remove the gas pressure manometer from the gas valve, and fully close the test port.  11.  Turn on the gas at the appliance’s manual gas valve.  12.  Ensure there are no gas leaks before reinstalling the front cover.   13.  Turn on the appliance by pressing the space above the dot. Completing and Affixing the Conversion Labels  1.  Fill in the conversion labels (included in the kit) associated with the new fuel type.  2.  Place the conversion labels onto the appliance at the positions indicated on the last page.  SFC 125 / SFB 125 - Fuel Conversion to Natural Gas - P-807...
  • Page 6 Clocking the Meter (for Natural Gas only)  1.  Turn off all other appliances and pilots  2.  Turn on the appliance and set the appliance to high fire.  3.  Ensure the appliance has a large load to heat, so that the appliance will not shut off.  4.  With a Stop-Watch, record the number of seconds for the smallest dial to make 1 full revolution.  5.  CFH = (3600 x Dial Size) / Seconds  6.  CFH x 1000 (check local Btu content) = Input Btu’s.   Note For 2 PSI meters multiply CFH x 1.097 For Metric meters multiply CFH x 35.3 For 2 PSI metric meters multiply CFH x 1.097 x 35.3 For Altitude above 4,500' deduct 2% per 1,000’ of altitude from the Input Btu’s. Where to Place Conversion Labels on the appliance...