IBC P-1609 Installation Instructions

Condensate pipe

Advertisement

P-1609 Condensate Pipe Replacement
Installation Instructions- CX
Warning
This replacement kit shall be installed by a qualified service agent in accordance with these
instructions and all applicable codes and requirements of the authority having jurisdiction. If the
information in these instructions is not followed exactly a fire, an explosion or production of
carbon monoxide may result causing property damage, personal injury or loss of life.
The qualified service agency is responsible for the proper installation of this kit. The installation
is not proper and complete until the operation is checked as specified in these instructions.
Danger
Never operate the combi boiler unless the trap is filled with water. Failure to comply will result in
severe personal injury or death.
Part #
251-223
255-159
150-029
190-309
190-310
150-438

When to Install the P-1609 Condensate Pipe Replacement Kit

Install the P-1609 kit if you need to replace a leaking or damaged condensate pipe on a CX unit.
IBC Technologies Inc.
Released Document
120-521E0
August 02, 2023
Condensate Pipe - CX
Description
Condensate Trap Bracket
Condensate Trap Bracket Seal
Screw, SHC, Zn, ¼-20 x ¾
EPDM Tubing, 1.5 x 1.25
PP-R Pipe 32 x 4.4
Hose Clamp, S/S, ¾ - 1¾
Quantity
1
1
2
1
1
2
|
1-844-432-8422
www.ibcboiler.com
1 of 4

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the P-1609 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for IBC P-1609

  • Page 1 150-438 Hose Clamp, S/S, ¾ - 1¾ When to Install the P-1609 Condensate Pipe Replacement Kit Install the P-1609 kit if you need to replace a leaking or damaged condensate pipe on a CX unit. IBC Technologies Inc. 1-844-432-8422 www.ibcboiler.com...
  • Page 2 A ladder or step may be required to have a clear vertical view of the work area. Do not attempt to remove the assemblies without a clear view, as damage to the connectors, screws or refractory may occur. IBC Technologies Inc. 1-844-432-8422 www.ibcboiler.com...
  • Page 3 EPDM tube to the heat exchanger condensate pan drain and one hose clamp (D) secures the EPDM tube to the PP-R pipe. 4. Pull the PP-R pipe (E) out from the condensate trap opening. IBC Technologies Inc. 1-844-432-8422 www.ibcboiler.com Released Document 120-521E0...
  • Page 4 2. Restore the call(s) for heat. 3. With the combi boiler operating, check for leaks. 4. Replace the front cover, and install the four Torx 20 screws on the top panel of the combi boiler. IBC Technologies Inc. 1-844-432-8422 www.ibcboiler.com...

Table of Contents