Safety
Important Regulatory and Installation Requirements
For installations in the Commonwealth of Massachusetts, the following local
requirements apply in addition to all other applicable NFPA requirements:
1) For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment, where the bottom of the
vent terminal and the air intake is installed below four feet above grade the following requirements must be satisfied.
1. If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide detector
and alarm shall be placed in the living area outside the bedroom(s). The carbon monoxide detector shall comply
with NFPA 720 (2005 Edition).
2. A carbon monoxide detector shall be located in the room that houses the appliance or equipment and shall:
a. Be powered by the same electrical circuit as the appliance or equipment such that only one service switch
services both the appliance and the carbon monoxide detector;
b. Have battery back-up power;
c. Meet ANSI/UL 2034 Standards and comply with NFPA 720 (2005 Edition); and
d. Have been approved and listed by a Nationally Recognized Testing Laboratory as recognized under 527
CMR.
3. A Product-approved vent terminal must be used, and if applicable, a Product-approved air intake must be used.
Installation shall be in strict compliance with the manufacturer's instructions. A copy of the installation
instructions shall remain with the appliance or equipment at the completion of the installation.
4. A metal or plastic identification plate shall be mounted at the exterior of the building, four feet directly above the
location of vent terminal. The plate shall be of sufficient size to be easily read from a distance of eight feet away,
and read "Gas Vent Directly Below".
Continued on following page.
6
Codes
The installation of this unit shall be in
accordance with local codes or, in the
absence of local codes, use
CAN/CSA-B149.1 or .2 Installation
Codes for Gas Burning Appliances for
Canada. For U.S. installations use the
National Fuel Gas Code ANSI Z223.1.
Always use latest editions of codes.
In Canada all electrical wiring is to be
done in accordance with the latest
edition of CSA C22.1 Part 1 and/or
local codes. In the U.S. use the National
Electrical Code ANSI/NFPA 70.
The heating contractor must also
comply with the Standard for Controls
and Safety Devices for Automatically
Fired Boilers, ANSI/ASME CSD-1 where
required by the authority having
jurisdiction.
Please carefully read this manual prior
to attempting installation. Any
warranty is null and void if these
instructions are not followed.
For information regarding other
Viessmann System Technology
componentry, please reference
documentation of the respective
product.
We offer frequent installation and
service seminars to familiarize our
partners with our products. Please
inquire.