Table 14: Simplicity SE Economizer Board Details (Continued)
Cover Label
C
COM
R
HOT
R
24V~
IN3
OAH
C
COM
R
24V~
IN4
SAH
C
COM
R
24V~
IN5
IAQ
C
COM
R
24V~
IN6
OAQ
C
COM
R
24V~
IN7
FR AIR
34
Description
24V~ IN Pin connections at right on upper edge of economizer board
24 VAC transformer Common referenced to
cabinet ground
24 VAC transformer HOT
ANALOG INPUTS Terminal on lower edge of economizer board
24 VAC hot supplied for the outdoor air
humidity sensor
0-10 VDC positive input from the Outdoor Air
Humidity sensor
24 VAC common/0-10 VDC negative for the
outdoor
air humidity sensor
24 VAC hot supplied for the supply air humidity
sensor
0-10 VDC positive input from the Supply Air
Humidity
sensor
24 VAC common/0-10 VDC negative for the
supply
air humidity sensor
24 VAC hot supplied for the indoor air quality
sensor
0-10 VDC positive input from the Indoor Air
Quality
sensor
24 VAC common/0-10 VDC negative for the
indoor air
quality sensor
24 VAC hot supplied for the outdoor air quality
sensor
0-10 VDC positive input from the Outdoor Air
Quality
sensor
24 VAC common/0-10 VDC negative for the
outdoor
air quality sensor
24 VAC hot supplied for the air monitoring
station sensor
ANALOG INPUTS Terminal on lower edge of economizer board
0-10 VDC positive input from the air monitoring
station sensor
Function & Comments
24 VAC common connection to power the economizer board.
Connects through circuit traces to C/COM terminals and pins
distributed on the economizer board.
24 VAC hot connection to power the economizer board.
Connects through circuit traces to R/24V~ terminals and pins
distributed on the economizer board.
Connects through circuit trace to 24V~ IN pin HOT
OAH parameter reports input status (0-100%H). Used in outdoor
air enthalpy
calculation for dual enthalpy economizer free cooling
changeover.
Connects through circuit trace to 24V~ IN pin COM
Connects through circuit trace to 24V~ IN pin HOT
SAH parameter reports input status (0-100%H). Unused in
current control revision.
Connects through circuit trace to 24V~ IN pin COM
Connects through circuit trace to 24V~ IN pin HOT
IAQRange parameter sets the CO2 parts per million measured
by the indoor air quality sensor when it outputs 10 VDC; IAQ
parameter reports input status (0-5000ppm). Used for demand
ventilation functions if the NetIAQ parameter indicates ?Unrel.
Connects through circuit trace to 24V~ IN pin COM
Connects through circuit trace to 24V~ IN pin HOT
OAQRange parameter sets the CO2 parts per million measured
by the outdoor air quality sensor when it outputs 10 VDC; OAQ
parameter reports input status (0-5000ppm). Used for demand
ventilation function when DVent-Mode selection is Diff between
IAQ and OAQ and the NetOAQ parameter indicates ?Unrel.
Connects through circuit trace to 24V~ IN pin COM
Connects through circuit trace to 24V~ IN pin HOT
MOA-Range parameter sets the cubic feet per minute/liters per
second measured by the air monitoring station sensor when it
outputs 10 VDC; Fr Air parameter reports input status (0-
50000CFM/23595lps). Used for economizer minimum position
reset in speed-controlled indoor blower applications.