201188 - 300 PORTAbLE POwER STATiON
Fault Code Failure Description
Charger input voltage is high, overvoltage
E32
protection
Car Charger output short circuit
E33
protection
Car Charger output over voltage
E34
protection
Car Charger output low voltage
E35
protection; or low voltage due to short
circuit, over current
The input voltage is lower than 12V when
E38
charging
12V DC module high temperature
E39
protection
The communication between the
E40
charging control chip and the MCU is
abnormal
Charging control chip high temperature
E41
protection
E44
USB Overvoltage protection
E45
USB Low voltage/short circuit protection
E48
QC3.0 with Overvoltage protection
QC3.0 with overcurrent/short circuit
E49
protection
The PD65W chip and control panel with
E50
abnormal communication.
E51
PD65W short circuit protection.
E52
PD65W high temp. protection.
E53
POWER button is disabled
E54
DC button is disabled
E55
AC button is disabled
E56
USB button is disabled
E57
LED button is disabled
Control panel and BMS abnormal
E72
communication
High temp. alarams when battery pack
E77
surface temperature ≥ 60 ° C
High temp. protection when battery pack
surface temperature ≥ 64 ° C, AC & 12V
E78
DC turn off ,the USB & PD port goes on
working.
E85
If the SOC is ≤5%, AC output turns off.
The over 60% of rated power is
E88
prohibitted at low temperature
POwER STATiON fAULT iNDiCATOR CODES
Diagnosis
Please use the standard charger to charge the power station, or ensure that
the input voltage is within the specified range.
Remove the load then reset the ports, Please contact customer service if the
problem still exists.
Disconnect the load then reset the ports, Please contact customer service if
the problem still exists.
Disconnect the load and restart the power station. Please contact customer
service if the problem still exists.
Please use the standard charger to charge the power station, or ensure that
the input voltage is within the specified range.
Please place the power station at room temperature and keep the vents
unobstructed. Use the power station after cooling
Disconnect the adapter and restart the power station. Please contact
customer service if the problem still exists.
Please place the power station at room temperature and keep the vents
unobstructed. Use the power station after cooling
Remove the load then reset the ports
Remove the load then reset the ports
Remove the load then restart the ports, the power station will be recovered.
Remove the load then restart the ports, the power station will be recovered.
Remove the load then restart the ports, the power station will be recovered.
Remove the load then restart the ports, the power station will be recovered.
Please place the power station at room temperature and Keep the vents
unobstructed. Use the power station after cooling
Press the button. Please contact customer service if the problem still exists.
Press the button. Please contact customer service if the problem still exists.
Press the button. Please contact customer service if the problem still exists.
Press the button. Please contact customer service if the problem still exists.
Press the button. Please contact customer service if the problem still exists.
Please restart the power station. Please contact customer service if the
problem still exists.
Please use the power station at room temperature or reduce AC load and Keep
the vents unobstructed.
Please place the power station at room temperature and Keep the vents
unobstructed. Use the power station after cooling
It will be eliminated after charging to SOC > 7%
Keep the power station at room temperature. Use the power station after the
temperature rises or reduce the discharge power