11-7. SELF-DIAGNOSIS
11-7-1. PAR-41MAA
1. Select ˝Service˝ from the Main menu,
and press the [SELECT/HOLD] button.
Select ˝Check˝ from the Service menu,
and press the [SELECT/HOLD] button.
Select ˝Diagnosis˝ from the Check menu,
and press the [SELECT/HOLD] button.
Select ˝Self check˝ with the F1 or F2 button,
and press the [SELECT/HOLD] button.
2. Select "Self check" from the Diagnosis menu, and press the
[SELECT/HOLD] button to view the Self check screen.
With the F1 or F2 button, enter the M-NET address, and
press the [SELECT/HOLD] button.
Check code, unit number, attribute, and indoor unit demand
signal ON/OFF status at the contact will appear. "-" will ap-
pear if no error history is available.
3. Resetting the error history
Press the F4 button (Reset) on the screen that shows the error history.
A confirmation screen will appear asking if you want to delete the error
history.
Press the F4 button (OK) to delete the error history. If deletion fails,
"Request rejected" will appear, and "Unit not exist" will appear if
indoor units that are correspond to the entered address are not found.
TCH124A
Self check
M-NET address
Error
Grp. IC
Contact
Off
Return: RETURN
Reset
52
Diagnosis
Self check
Remote controller check
Service menu: MENU
Cursor
F1
F2
F3
F4
SELECT
MENU
RETURN
HOLD
S
e
f l
c
h
e
k c
M-NET address
S
e
e l
c
: t
SELECT
A
d
d
e r
s s
When there is no error history
Self check
M-NET address
-
Error
Grp.
----
--
Contact
Off
Return: RETURN
Reset
Self check
M-NET address
Delete error history?
Cancel
OK
Self check
M-NET address
Error history deleted
Return:RETURN
ON
OFF