8-4. HEAT OPERATION
RETURN SELECT
MENU
HOLD
.
Control Mode
1. Temperature
1-1. Determining temperature adjustment function (Function to prevent restarting for 3 minutes)
adjustment
• Room temperature
function
• Room temperature
2. Fan
By the remote controller setting (switch of 4 speeds+Auto)
4 speeds + Auto type
When [Auto] is set, fan speed is changed depending on the value of:
∆T = Set temperature − Room temperature
Give priority to under-mentioned controlled mode
2-1. Hot adjust mode
2-2. Residual heat exclusion mode
2-3.
2-4. Cool air prevention mode (Defrosting mode)
TCH124A
<How to operate>
ON
OFF
<How to operate>
Control Details
Set temperature −2°F ···Thermo-ON
Set temperature ···Thermo-OFF
Type
Auto
Press ON/OFF button.
Press [F1] button to display HEAT.
Press [F2] [F3] button to set the set temperature.
NOTE: The settable temperature range varies with the model of
outdoor units and remote controller.
Press POWER ON/OFF button.
Press the operation MODE button to display HEAT.
Press the TEMP. button to set the set temperature.
NOTE: The set temperature changes 1°F when the
button is pressed one time. Heating 63 to 83°F
Fan speed notch