BACnet Communication Settings:
The Rinnai PURE controller is capable exposing data over a BACnet MS/TP network. It is important that
each device has the correct network settings. Follow the below instructions to do this:
NOTE: Incorrect network settings will result in a conflict of communications and prevent the Gateway
from operating correctly.
1.
Press and hold all 4 buttons on the PURE controller for approx. 5 seconds. The maintenance
screen will show.
2.
Using the left hand buttons scroll down to the Setup Menu option. Once highlighted, select this
option with the top right hand side button on the Pure Controller.
3.
Select Unit Specific using the top right button again.
4
Select CCI. This will show the current software and Network settings of the PURE Controller
Programing Instructions
Maintenance Menu
Input Status
Output Status
Scheduler
Global Settings
User Interface
Setup Menu
Exit Menu
Setup Menu
Unit Specific
Input Status
Maintenance Menu
Configuration Menu
Exit Menu
Unit Specific
CCI
Return to previous