Rinnai RS100 Operating And Installation Instructions

Control system
Hide thumbs Also See for RS100:

Advertisement

Quick Links

Rinnai
Control system
For the heating specialist
Operating and installation instructions
Room control unit RS100

Advertisement

Table of Contents
loading

Summary of Contents for Rinnai RS100

  • Page 1 Rinnai Control system For the heating specialist Operating and installation instructions Room control unit RS100...
  • Page 2: Table Of Contents

    Contents General safety instructions ............3 Safety measures for electric - compliant installation ....3 Installation of the room control unit ..........5 Mounting location ....................5 Mounting instructions ...................5 Electrical connection ....................6 Electrical connection at boiler................6 Accessories ..................7 Outdoor sensor ....................7 Resistance values of outside sensor..............7 Commissioning of the room control unit.........8 Language ......................8 Code input......................8...
  • Page 3: General Safety Instructions

    General safety instructions 2. When installing the room control unit a minimum distance of 15.75 in (40 cm) All electrical connections and safety must be maintained to other electrical measures have to be carried out by a utilities with electromagnetic emissions, specialist in due consideration of valid such as power...
  • Page 4 4. It is suggested to use a shielded cable 6. The outside sensor may not be for all installations. installed close transmitting receiving equipment (on garage walls close to receivers for radio-controlled 5. The shielding of the cable has to be garage door openers, amateur radio connected with earth potential, i.e.
  • Page 5: Installation Of The Room Control Unit

    Installation of the room control – on non-insulated outside walls unit – in corners or wall recesses, shelves or behind curtains (insufficient ventilation) – close to doors of unheated rooms (influence of low temperatures) – on unsealed flush-type boxes (influence of external low temperatures due to the chimney effect of installation tubes) –...
  • Page 6: Electrical Connection

    Electrical connection Electrical connection boiler The 2-strand data bus cable is connected The electrical connection depends on the to terminals A and B of the 2-pole terminal type and version of the respective heating strip on the bottom plate. generator and takes place directly at the terminals A and B in the corresponding boiler control or interface.
  • Page 7: Accessories

    Accessories 5– Establish the electrical connection. To this end, preferably use a 2-strand Outdoor sensor cable with a minimum cross-section of 1 mm (18 AWG). The connection is made at the 2 screw terminals inside the sensor case and may be interchanged. 6–...
  • Page 8: Commissioning Of The Room Control Unit

    Commissioning of the room Code input control unit Installer code Language After entering the installer code all parameters determined for the heating During the first activation or with each specialist are released and can be edited return of voltage after a power failure all in accordance with the system version.
  • Page 9 Alarm messages Alarm message register In order to be able to perform an exact The room control unit is provided with an diagnose in case of a problem the control alarm message register, which is able to system is equipped with a comprehensive hold maximum 20 alarms.
  • Page 10: Site Information

    Site information A - Site and system temperatures If set value is displayed in the following After accessing the information level using the table in the category "display value", it will information key , all available site- and appear when the rotary pushbutton is system temperatures can be requested one pushed.
  • Page 11: Parameter Synoptic

    Parameter synoptic Entry into the level selection: Hold rotary push-button pressed for approx. 3 seconds - automatic call of time programs Select required level via rotary push-button and confirm, enter code if necessary Programming Configuration Control circuits Service TIME DHW-NIGHT RED.
  • Page 12: Overview Of Installer Parameters And Adjustment Options

    Overview of installer parameters and adjustment options HYDRAULIC Level The parameters of this level refer to the general hydraulic system of the boiler as well as to the functionality and configuration of the programmable inputs and outputs for the corresponding boiler components. Parameter Designation Setting range / Setting values...
  • Page 13 Fahrenheit range OFF, ON Shown on display screen only Message from system interlocks Messages from interlocks and Alarm messages system blockages into the system handling Message from interlocks, Automatic boiler control blockages and warnings into the system Alarm message memory 2 OFF, ON in dependence on access code only to Reset to factory values...
  • Page 14 Adaptation heating curve OFF, ON (not during HC = constant control) OFF, 1 ... 16 h Inrush optimization OFF, 0,5...40,0 K (not during HC= constant Heating limit contr.) Room frost protection 10 °C 5 ... 30 °C temperat ure Room thermostat function OFF, 0.5 ...
  • Page 15 ALARM 2 Level (..C..)* In this level up to 20 alarm messages can be stored, these are permanently updated. Parameter Designation Setting range / Setting values Last alarm message Alarm message #1 Alarm message #2 Next to last alarm message …...
  • Page 16 Notes 100000157 9/2009...