OPERATIONAL COMPONENTS
Mode Selection options:
Schedule:
The PURE controller will operate to the programmed schedule that has been set within the controller
Override ON:
The PURE controller will be overridden on to an occupied condition for the override time set in the
maintenance menu. During this mode the pasteurisation cycle will not operate.
To set or edit the override time press all four buttons on the PURE controller to enter the maintenance
menu, navigate to Global Setting > Override ON. The Override ON setting is adjustable from 15-300
minutes in 15 minute steps.
Temporary Override:
The PURE controller will be OFF until the next scheduled Occupancy ON or Pasteurisation ON period
Permanent Override:
The PURE controller can be set to run in 3 different modes during Permanent Override operation:
1.
None – Both Occupied and Pasteurisation control is inhibited.
2.
OCC – The PURE controller will always be overridden ON and will operate to the occupied set
point. Pasteurisation will not run in this mode.
3.
Pas – If set in the schedule, only the pasteurisation will run when called for.
To set or edit the Permanent Override settings, press all four buttons on the PURE controller to enter
the maintenance menu, navigate to Global Setting > Override Off.
Programing Instructions
11