Download Print this page

Immergas VICTRIX PRO 35 V2 Installation Set page 6

Plate exchanger kit
Hide thumbs Also See for VICTRIX PRO 35 V2:

Advertisement

Kit cod. 3.033678
Volumi contenuto d'acqua nel kit in abbinamento alla:
Volumes of water content in the kit in combination with:
Modello/
Model
N° 2 Victrix Pro 35 V2
N° 3 Victrix Pro 35 V2
N° 4 Victrix Pro 35 V2
N° 5 Victrix Pro 35 V2
N° 2 Victrix Pro 55 V2
N° 3 Victrix Pro 55 V2
N° 4 Victrix Pro 55 V2
N° 5 Victrix Pro 55 V2
N° 2 Victrix Pro 80 V2
N° 3 Victrix Pro 80 V2
N° 4 Victrix Pro 80 V2
N° 5 Victrix Pro 80 V2
Dati Tecnici/Technical data
Scambiatori a piastre in
N° piastre/
abbinamento a
N° plates
VICTRIX PRO V2 /
Plates exchangers
paired with
VICTRIX PRO V2
(kW)
175
90
200
90
250
90
275
90
300
90
350
90
400
90
Contenuto litri impianto/
System litres content
Massima potenza
Portata Primario /
gestita/
Primary flow rate
Maximum power
(m
/h) M/R 80°/60°
3
(kW)
400
7.6
400
8.6
400
10.7
400
11.8
400
12.9
400
15.0
400
17.2
Legenda:
F1 - Mandata dalla caldaia
F2 - Mandata all'impianto
F3 - Ritorno dall'impianto
F4 - Ritorno alla caldaia
F5 - Caldaia primario
F6 - Impianto secondario
Key:
F1 - Flow from boiler
F2 - Flow to system
F3 - Return from system
F4 - Return to boiler
F5 - Boiler primary circuit
F6 - System secondary circuit
25
34
43
52
26
35
45
54
27
37
46
56
Portata Secondario /
Secondary flow rate
(m
/h) M/R 70°/55°
3
Circuito prima-
rio ΔT 20°C/
Primary circuit
ΔT 20°C
10.0
11.5
14.3
15.7
17.2
20.0
22.9
Capacità vaso espansione (litri)/
Expansion vessel capacity (litres)
4
4
8
8
4
4
8
8
4
4
8
8
Δp (m.c.a.)
scambiatore
Circuito seconda-
rio ΔT 15°C
Secondary
circuit ΔT 15°C
0.23
0.4
0.3
0.52
0.46
0.82
0.6
0.99
0.67
1.18
0.9
1.6
1.2
2.1
3
Peso solo
/ Weight
of the heat
exchanger
only
(kg)
31.3
31.3
31.3
31.3
31.3
31.3
31.3

Advertisement

loading